ELECTRICAL SPECIFICATIONS
35/62
EWAT~B-SR
MODEL
EWAT330B-
SRA2
EWAT340B-
SRA1
EWAT420B-
SRA2
EWAT460B-
SRA2
EWAT510B-
SRA2
POWER SUPPLY
Phases
No.
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
578
565
575
638
712
717
Nominal running current
cooling
A
216
202
231
245
298
324
Maximum running current
A
259
248
256
324
398
405
Maximum current for wires
sizing
A
285
273
281
356
437
445
FANS
Nominal running current
cooling
A
11
13
11
15
15
17
COMPRESSORS
Phases
No.
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
Maximum running current
A
248
235
245
309
383
387
Starting method
DOL
DOL
DOL
DOL
DOL
DOL
MODEL
EWAT570B-
SRA2
EWAT610B-
SRA2
POWER SUPPLY
Phases
No.
3
3
3
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
UNIT
Maximum inrush current
A
791
795
800
Nominal running current
cooling
A
378
402
414
Maximum running current
A
478
485
494
Maximum current for wires
sizing
A
526
534
544
FANS
Nominal running current
cooling
A
17
19
24
COMPRESSORS
Phases
No.
3
3
3
Voltage
V
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
Maximum running current
A
461
466
470
Starting method
DOL
DOL
DOL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Please refer to unit nameplate data.