Field settings ESiEN02–01A
4–10 Part 4 Commissioning and Test Run
3
1
4
5
2.2 How to Change the Field Settings with the Wired Remote Control
Installation
conditions
The field settings have to be changed with the remote control according to the installation conditions.
Wired remote
control
The illustration below shows the wired remote control.
Components The table below contains the components of the wired remote control.
TEST
C
hr
hr
TEST
NOT
AVAILABLE
L H
2
10
11
3
1
4
5
6
7
8
14
15
16
17
18
19
20
21
22
12
9
13
No. Component No. Component
1 ON/OFF button 12 Display Defrost
2 Operation lamp (red) 13 Non-functioning
3 Display Under centralized control 14 Timer mode start/stop button
4 Ventilation/air cleaning 15 Timer ON/OFF button
5 Operating mode 16 Inspection/test operation button
6 Inspection/test operation 17 Programming time button
7 Programmed time 18 Temperature setting button
8 Set temperature 19 Filter counter reset button
9 Fan speed 20 Fan speed control button
10 Air flow flap 21 Operating mode selector button
11 Time to clean air filter 22 Air flow direction adjust button