Daikin RXYQ24M7W1B [95/344] Cooling operation fan control

Daikin RXYQ24M7W1B [95/344] Cooling operation fan control
Basic Control SiE39-404
84 Function
2.4 Cooling Operation Fan Control
In cooling operation with low outdoor air temperature, this control is used to provide the
adequate amount of circulation air with liquid pressure secured by high pressure control using
outdoor unit fan.
STEP7
STEP6
STEP5
STEP4
STEP3
STEP2
STEP1
STEP9
Pc<2.8MPa
Pc: HP pressure sensor detection value
Pc>3.1MPa
Pc>3.3MPa
Pc<1.8MPa
Pc<2.7MPa
Pc>2.7MPa
Pc>3.2MPa
Pc<1.8MPa Pc>2.7 MPa
Pc<1.8MPa Pc>2.7 MPa
Pc<1.8MPa Pc>2.7 MPa
Pc<1.8MPa Pc>2.7 MPa
Pc<1.8MPa Pc>2.7 MPa
Pc<2.3MPa Pc>2.7 MPa
STEP8-1
STEP8-2
Fan Steps
RXYQ5M
RXYQ
8 and 10M
RXYQ
12 to 16M
STEP1 0rpm 0rpm 0rpm
STEP2 300rpm 300rpm 300rpm
STEP3 320rpm 320rpm 325rpm
STEP4 350rpm 345rpm 355rpm
STEP5 385rpm 385rpm 400rpm
STEP6 470rpm 465rpm 500rpm
STEP7 585rpm 575rpm 630rpm
STEP8-2 800rpm 660rpm 710rpm
STEP8-1 800rpm 785rpm 880rpm
STEP9 840rpm 825rpm 920rpm