Daikin RX38MTLE [120/255] Inverter compressor fails three times a month

Daikin RX36MY1 [120/255] Inverter compressor fails three times a month
VRV in General SiE30-408
116 Cases for Examination
1.12 Inverter Compressor Fails Three Times a Month
Applicable
Models
VRV in general
Condition
Cause
Due to foreign matters clogging between the oil separator and the filter, oil does not return to the
compressor.
Measure Recovers by replacing the refrigerant filter.
Point of
Diagnosis
Measure temperature before and after the oil-returning capillary connection of the suction pipe
and obtain the temperature difference. Check that the temperature difference is 5 degrees or
more when the compressor operating frequency is stabilized.
1.13 Cooling Operation of Specific Indoor Units is not Good.
Applicable
Models
VRV in general
Condition Cooling operation of specific indoor units only is not good though remaining indoor units work
well and reach the set temperature.
The pressure of the outdoor units for low-pressure use (evaporating temperature) has reached
the target value.
Liquid pipe temperature of the faulty indoor units is 4 to 5°C and gas pipe temperature is 18 to
22°C.
Cause Liquid pipe at the inlet of indoor unit was bent by hands and broken. It caused lacking in gas
supply because essential refrigerant circulation amount was not secured for the indoor units.
Measure Recovers by correcting the field piping.
Point of
Diagnosis
1. Check the following:
Make sure that the difference between thermistor temperature of indoor unit’s gas pipe and
thermistor temperature of liquid pipe is applox. 5°C.
(Thermistor temperature of indoor unit's liquid pipe: 5 to 8°C; Thermistor temperature of gas
pipe: 10 to 13°C)
2. Check whether the pressure of outdoor unit for low-pressure (evaporating temperature) is
approx. 0.4 MPa.
Oil separator
Suction pipe
A
B
Compressor
A+5°C < B or more