Cases for Examination 121
2. Indoor Unit Related Examples
2.1 Temperature is not Displayed on the Central Controller.
Applicable
Models
FXMQ125MF + controller
Condition Though the FXYMP140MF (outside air processing unit) was built in the control range of the
centralized controller, no temperature is displayed on the centralized controller. Temperature is
displayed on the remote controller.
Cause Since the outside air processing air conditioner is controlled based on the discharge air, set
temperature of the discharge air is displayed on the remote controller. (Type M or later models)
Therefore, temperature is not displayed on the centralized controller due to the difference in
meaning of set temperature compared with the normal indoor units.
Measure Explain that the contents of display are normal.
Point of
Diagnosis