SiE30-408 Adaptors for Connection of Air Conditioners
Appendix 203
2. Setting of CONTROL MODE selector switch (RS1)
1 To use the system only for display function only in individual display mode
2 To operate the system using constant input to the input A
Caution The input B is used for forcedly OFF. If this input B is turned ON, the system will be put into
“Stop + Remote controller inhibited”, thus disregarding the input A. Even if the input A is turned
ON with the input B in an OFF state, the content with the input A turned ON will not be provided.
In this case, the input A should be turned ON again.
3 To operate the system using instantaneous input to the input A
(Use instantaneous input with ON time of 200 msec or more for the input A.)
To conduct demand control using input B
Forcedly thermostat OFF command
This command is used to operate the indoor unit only in forcedly fan mode.
Energy saving operation command (*)
This command is used to operate the system with set temperature increased by 2°C in
cooling operation or decreased by 2°C in heating operation.
Caution In this case, even though the input A is turned ON, the system will make a stop, thus
stopping all units in one and the same group.
* On the SkyAir series, even though Position D or F is selected, the forcedly thermostat OFF
command will be issued.
Position Function
0 Individual display (with input ignored)
Use the CONTROL MODE selector switch (RS1)
to make selection and setting of control mode
through input A or B.
(Factory set)
0 position
CONTROL MODE
SELECTOR SWITCH
RS1
Position Function Contents with input A tuned ON
Contents with input
A turned OFF
1
Remote controller
inhibited
Operation (The remote controller is inhibited
at all times.)
Stop + Remote
controller inhibited
2 Centralized priority Operation + Remote controller permitted
3
Remote controller
stop permitted
Operation + Only remote controller stop
permitted
(Operation from remote controller is
disabled.)
4
Remote controller
permitted / stop
Remote controller permitted
(Operation from remote controller is
impossible.)
Position Function Contents of input A Function of input B
5
Remote
controller
inhibited
Stops if the input A is turned ON while in
operation.
Operates if the input A is tuned ON while in stop.
The input B will be
put into forcedly
OFF function mode.
(If the input B is
turned ON, the
system will be put
into “Stop + Remote
controller inhibited,
Input A
disregarded”.)
6
Last-pressing
priority
Stops if the input A is turned ON while in
operation.
Operates if the input A is tuned ON while in stop.
(The remote controller is permitted at all times.)
Position Functions & contents with input A turned ON Functions with input B turned ON
C
Remote controller inhibited
(Same as Position 5)
Forcedly thermostat OFF command
D Energy saving operation command (*)
E
Last-pressing priority
(Same as Position 6)
Forcedly thermostat OFF command
F Energy saving operation command (*)