Daikin REYQ46M7W1B [135/405] This equipment can use the addresses between 1 00 and 4 15 it is impossible to use address 5 00 and subsequent addresses and use any address in duplication example when the top address was set to 4 14 the number of facility equipment cannot be set to 4 in this case set it to 1 or 2

Daikin REYQ46M7W1B [135/405] This equipment can use the addresses between 1 00 and 4 15 it is impossible to use address 5 00 and subsequent addresses and use any address in duplication example when the top address was set to 4 14 the number of facility equipment cannot be set to 4 in this case set it to 1 or 2
2.3 Dio Unit <DEC102A51> 131
ED721208 Adaptor
4
ON
ON ON ON
This indicates
the switch knob.
ON
RS2DS1
<Example>
When Address No.
is set to 1-08
Control range DS1 (high order)
setting (Address range)
High
order: 1
B
11
0
00
1
01
1-00 ~ 1-15Control range DS1
6
06
A
10
8
08
7
07
RS1 Switch Setting Table
Position
Address No.
Address No. indicates
the following portion in
this case.
F
15
3
03
4-00 ~ 4-15
when a product is
discharged from the factory
1-8
2-00 ~2-15
C
12
(low order)
5
05
3-00 ~ 3-15
4
04
Low
order: 8
E
14
2
02
High
order
Low
order
D
13
9
09
8
when a product is discharged from the factory
Set the top address of this equipment with the DIII-NET setting switch (DS1/RS1).
Set Address No. (low order) with the centralized address setting switch (RS1).
Referring to the table below, set the address number low order.
(Address Nos. are 1-00, 1-01, --- 1-15, 2-00, --- 4-15.)
In this case, it follows that this equipment uses
Address Nos. 1-08 to 1-11. (4 numbers max.)
Number of centralized addresses used
The number of centralized addresses used is determined by the top address set in this paragraph and the number
of facility equipment connected that is set in "
TP1 Setting (Facility equipment quantity change)" paragraph.
Example 1: When the top address was set to "1-00" and the number of facility equipment was set to "2",
it follows that "1-00" and "1-01" are being used.
Example 2: When the top address was set to "3-15" and the number of facility equipment was set to "4",
it follows that "3-15", "4-00", "4-01" and "4-02" are being used.
<CAUTION>
This equipment can use the addresses between "1-00" and "4-15".
(It is impossible to use Address 5-00 and subsequent addresses, and use any address in duplication.
Example: When the top address was set to "4-14", the number of facility equipment cannot be set to "4".
In this case, set it to "1" or "2".)
This switch selects whether the input is abnormal with the abnormal input contact (A1 to A4) open or closed.
OFF (factory preset before shipment) --- Abnormal in the open condition
ON --- Abnormal in the closed condition
The relationship between each switch and abnormal input is as described below.
Input A1: DS2-1 Input A2: DS2-2
Input A3: DS2-3 Input A4: DS2-4
DS2 Setting
Using the DIII-NET setting switch (DS1), set the range of Address No. that is set in this equipment.
Address Nos. 1-00 to 1-15 are factory controlled before shipment.
DS4-1 Setting
This switch selects the control output status after power failure occurred in this equipment and the power
was recovered.
OFF (factory preset before shipment) --- The control power after power recovery is handled as stop output.
ON --- The control output after power recovery is handled as output before power failure.