Daikin REYQ46M7W1B [151/405] Ed721208 installation manual

Daikin RXQ24PAY1 [151/405] Ed721208 installation manual
147
ED721208 Installation Manual
5
16
Installation Manual 3P291714-1
DCM601A51 intelligent Touch Manager
English
NOTE
r 9JCVoUCTGOQVGEQPVTQNNGTITQWR!
A single remote controller can simultaneously control a maximum of 16 indoor units.
This capability is referred to as group control. A remote controller group is a group of
indoor units controlled under the same remote controller.
[Conceptual drawing of a remote controller group]
F1, F2 P1, P2 F1, F2 P1, P2 F1, F2 P1, P2
F1, F2 P1, P2
A
A Max. 16 units
2.2.2 4GSWKTGOGPVUVJCVOWUVDGOGV
%CDNGURGEKƂEC-
tions
r Cable type: 2-core vinyl-insulated vinyl-sheathed cable/vinyl cabtyre cable or 2-core
shielded cable
r Core thickness: 0.75mm² - 1.25mm²
r 6GTOKPCNVTGCVOGPV7UGCTQWPFETKORV[RGVGTOKPCN/YKVJKPUWNCVKPIUNGGXG
Precautions r Do not use multicore cables with three or more cores.
r When using a shielded cable, connect only one end of each shield wire to the ground.
r The maximum wire distance must be kept to 1000 meters or less. The total wire length
must be limited to 2000 meters, except when using a shielded cable whose total wire
length must be kept to 1500 meters or less.
2.2.3 2TGECWVKQPUHQTWUKPIOWNVKRNGEGPVTCNK\GFEQPVTQNNGTU
Equipment that controls multiple air conditioners is referred to as “centralized controller”.
&#+-+0oURTQFWEVRQTVHQNKQKPENWFGUCYKFGTCPIGQHEGPVTCNK\GFEQPVTQNNGTUUWKVGFVQFKHHGT-
ent applications or target sizes, which can be used in combination to construct an optimal
air conditioning control system.
+HVYQQTOQTGEGPVTCNK\GFEQPVTQNNGTUCTGWUGFKPEQODKPCVKQPKP&+++0'6[QWOWUVGUVCD-
lish a MASTER to SLAVE relationship among those controllers to prevent confusion. The
MASTER authority may be assigned to one controller only. The remaining controllers must
be set to SLAVE.
The intelligent Touch Manager is set to MASTER by default. Change the setting to SLAVE
in any of the following cases:
r Where Interface for use in BACnet is installed in parallel.
r 9JGTG+PVGTHCEGHQTWUGKP.10914-5KUKPUVCNNGFKPRCTCNNGN
r Where there is another MASTER intelligent Touch Manager or MASTER iTM plus adap-
tor, and it is connected in relations of main/sub.