Daikin REYQ46M7W1B [38/405] Centralized control equipments which can use with intelligent touch manager

Daikin RXY30MTL [38/405] Centralized control equipments which can use with intelligent touch manager
34
Fundamental of DIII-NET ED721208
6.
Centralized control equipments which can use with intelligent Touch Manager
Following centralized control equipments can connect to the same DIII-NET with an intelligent Touch Manager.
Centralized control equipment Description
DMS502B51(Interface for use in BACnet
®
) or
DMS504B51(Interface for use in L
ON
W
ORKS
®
)
One of these interfaces can connect to the same DIII-NET.
DIII MASTER switch of intelligent Touch Manager should be set to
“SLAVE”.
DMS601A51 (intelligent Touch Manager) or
DMS601A52 (iTM plus adaptor) or
DCS302CA61 (Central remote controller)
One of these controllers can connect to the same DIII-NET.
-DIII MASTER switch of DMS601A51 and DMS601A52 should be
set to “SLAVE”.
-DIII MASTER connector of DCS302CA61 should be removed.
-These controllers have to be set to “SLAVE”.
DCS301BA51 (Unified ON/OFF controller) Totally 8 DCS301BA51 can connect to the same DIII-NET.
Refer to DCS301BA51 installation manual for setting.