Daikin REYQ46M7W1B [245/405] Ed721208 commissioning manual

Daikin RXQ44PAHY1 [245/405] Ed721208 commissioning manual
241
ED721208 Commissioning Manual
6
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
36
3. %58ƂNGHQTOCV
6JGHQTOCVQHVJG%58ƂNGQWVRWVHTQOVJGK6/KUCUUJQYPDGNQY#%58ƂNGQWVRWVYJGPPQ
management point data is registered can be used as a template for new implementations since
only the area used by the system and the header portion are output.
The following table shows the CSV format for management point data registration.
r 0WOGTKEXCNWGUKPFKECVGFKPGCEJKVGOEQTTGURQPFVQVJGEQNWOPPWODGTKPVJG%58ƂNGVJGƂTUVEQNWOPKUƂZGFCPFWUGFHQTFCVCV[RG
KFGPVKƂECVKQP$NCPMKVGOUKPFKECVGVJGTGKUPQCRRNKECDNGFCVC
%NCUUKƂECVKQP
Keyword Description Value
Management point type
Di Pi D3Di D3Dio
Indoor
unit
Outdoor
unit
Internal
Ai
Ventilator Chiller
Internal
Pi
BACnet
Di
BACnet
Dio
BACnet
Ai
BACnet
Ao
Common
Header type
KFGPVKƂECVKQP
DI-H PI-H D3DI-H
D3DIO-H
IN-H OUT-H
INTERNAL
AI-H
HRV-H
CHIL-H
INTERNAL
PI-H
BACNET
DI-H
BACNET
DIO-H
BACNET
AI-H
BACNET
AO-H
&CVCV[RGKFGPVKƂECVKQP
DI-D PI-D D3DI-D
D3DIO-D
IN-D OUT-D
INTERNAL
AI-D
HRV-D
CHIL-D
INTERNAL
PI-D
BACNET
DI-D
BACNET
DIO-D
BACNET
AI-D
BACNET
AO-D
POINTID Management point ID 101 to 1000000 2
NAME Name
String (1 to 12 characters regardless of single or double byte)
3
DETAILEDINFO Detailed information
String (0 to 50 characters regardless of single or double byte)
4
PROHIBITOP
Prohibit manual
operation
0: Allowed, 1: Prohibited 5 5 5 5 5 5
PORTNO Port number
D3, Internal Pi, Main unit: 1 to 8
External: 1 to 30
555665 6 6 5
ADDRESS1
Upper level address
(group)
D3: 1 to 4
External: 1 to 120
Internal Pi: 1 to 127
Outdoor unit: 1 to 127
Main unit: 1 to 4 (2 to 4 for Port 1)
666776 7 7 6
ADDRESS2
Lower level address
(unit)
D3Dio, D3Di, Indoor unit, Ventilator,
Chiller: 0 to 15
788 8 8
STARTSTOPMON ON Status Monitor
External Di: 1 to 120
External Dio: ON Status Monitor address 1 to 120
0QVURGEKƂGF
NORMALABNORMALMON
0QTOCN#DPQTOCN
Monitor
0QTOCN#DPQTOCN/QPKVQT+PRWVCFFTGUUVQ
0QVURGEKƂGF
STARTSTOP 101((QRGTCVKQP 0: Always 1: Instant
STARTSTOPADDR1 5VCTV5VQRCFFTGUU
Always: 1 to 120
Instant: ON address 1 to 120
STARTSTOPADDR2 5VCTV5VQRCFFTGUU
Always: Handled as invalid
Instant: OFF address 1 to 120
SERVERINST
BACnet Server Device Instance
0 to 4194302 5656
STATOBJTYPE Status Object Type* VQ0QVWUGFŨ 676
STATOBJINST Status Object Instance* VQ0QVWUGFŨ 787
OPOBJTYPE Operation Object Type* VQ0QVWUGFŨ 97
OPOBJINST
Operation Object
Instance*
VQ0QVWUGFŨ 10 8
ERROBJTYPE Error Object Type* VQ0QVWUGFŨ 811
ERROBJINST Error Object Instance* VQ0QVWUGFŨ 912
ICON Icon ID 100 to 999 7 7 8997 5 9 9 7 101389
ANADDR ACNSS Address Indoor unit (2 to 128, 1: Invalid) 10
Monitoring
COMMONLV
Communication error monitoring level
1: Monitoring, 2: Monitor + History 8 8 9 10 11 10 10 11 14 9 10
* Set to -1 when not used.
The item is regarded as not used if either the Object Type or Object Instance value is set to –1.
For information on the Object Type, refer to the applicable guideline (ISO16484-5).
Output only when BACnet (optional) is enabled.
Output only when BACnet (optional) is enabled.