[Stop Valve Operation Procedure]
When operating the stop valve, follow the procedure instructed below.
Note:
Do not open the stop valve until “1.2.1 Check work prior to turn power supply on” in page
157 are completed. If the stop valve is left open without turning on the power, it may cause
refrigerant to buildup in the compressor, leading insulation degradation.
Be sure to use the correct tools.
The stop valve is not a back-seat type. If forced it to open, it might break the valve body.
When using a service port, use the charge hose.
After tightening the cap, make sure no refrigerant gas is leaking.
[Tightening torque]
The sizes of the stop valves on each model and the tightening torque for each size are listed in
the table below.
<Size of Stop Valve>
REYQ8~16PY1B
REYQ18~48P7Y1B
8HP type 10HP type 12HP type 14HP type 16HP type
Liquid pipe stop valve
φ9.5
φ12.7
The 12HP type corresponds to the 12.7-
diameter onsite piping using the accessory
pipe.
Suction gas stop valve
φ25.4
The 8HP type corresponds to the 19.1-diameter onsite piping using the
accessory pipe.
The 10HP type corresponds to the 22.2-diameter onsite piping using the
accessory pipe.
The 12-16 HP type corresponds to the 28.6-diameter onsite piping using
the accessory pipe.
HP/LP gas stop valve
φ19.1
The 8HP type corresponds to the 15.9-diameter onsite piping using the
accessory pipe.
The 14·16 HP type corresponds to the 22.2-diameter onsite piping using
the accessory pipe.
8HP type 10HP type 12HP type 14HP type 16HP type
Liquid pipe stop valve
φ9.5
φ12.7
The 12HP type corresponds to the 12.7-
diameter onsite piping using the accessory
pipe.
Suction gas stop valve
φ25.4
The 8 · 10HP type corresponds to the 22.2-diameter onsite piping using
the accessory pipe.
The 12-16 HP type corresponds to the 28.6-diameter onsite piping using
the accessory pipe.
HP/LP gas stop valve
φ19.1
The 14 · 16 HP type corresponds to the 22.2-diameter onsite piping
using the accessory pipe.
Equalizer pipe stop valve φ19.1