Daikin REYQ14PY1B [340/477] Troubleshooting

Daikin REYQ16PY1B [340/477] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiBE37-701_B
329 Troubleshooting
Troubleshooting
Continued from the previous page.
(Start failure due to aged operation.)
Check 4
Check if the
power transistor
is normal.
NO
Cancel the sleeping state of
refrigerant.
: Referring to the information on P384.
Check 4
Refrigerant is
sleeping. (The unit is
out of power supply
for more than 6
hours.)
Check if the
insulation resistance
of the compressor is
100k
or over.
Broken inside the
compressor
YES
NO
YES
NO
YES
Replace the inverter compressor.
Replace the inverter compressor.
Replace the compressor inverter
PCB.
Recheck the compressor/
refrigerant circuit.
NO
YES

Содержание

Скачать