Troubleshooting by Indication on the Remote Controller SiBE37-701_B
325 Troubleshooting
3.41
L8
Outdoor Unit: Momentary Overcurrent of Inverter
Compressor
Remote
Controller
Display
L8
Applicable
Models
REYQ8P~48P
Method of
Malfunction
Detection
Malfunction is detected from the current flowing in the power transistor.
Malfunction
Decision
Conditions
When overload in the compressor is detected. (Inverter secondary current 16.1A)
(1) 19.0A and over continues for 5 seconds.
(2) 16.1A and over continues for 260 seconds.
Supposed
Causes
Compressor overload
Compressor coil disconnected
Defect of inverter PCB
Faulty compressor