Daikin REYQ14PY1B [275/477] Troubleshooting

Daikin REYQ16PY1B [275/477] Troubleshooting
SiBE37-701_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 264
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Remove the foreign matters.
Turn OFF the power
supply, and then wait for a
period of 10 minutes.
Are there any
foreign matters
around the fan?
NO
YES
NO
NO
YES
YES
NO
YES
Is the connector (X20A)
for the fan motor properly
connected to the indoor
unit PCB? (*1)
Properly connect the connector.
By disconnecting the
connector (X20A) for the
fan motor from the
indoor unit PCB, the fan
can be lightly rotated by
hand.
Replace the fan motor.
Disconnect the connector
from the fan motor, and then
make measurement of
resistance between pins.(*2)
Is the resistance between
the pins not less than the
judgement criteria?
Replace the fan motor.
Replace the indoor unit PCB.
*1. If any junction connector is provided between the
connector (X20A) on the indoor unit PCB and the fan
motor, also check whether or not the junction
connector is properly connected.
*2. All resistance measuring points and judgement criteria
FXAQ
20~63PV1
1 White
2 Orange
3 Brown
4 Blue
5
6
7 Red
FG
Vsp
Vcc
GND
Vdc
FXFQ
20~125P8VE
1
2
3
FG
4
Vsp
5
Vcc
Vdc
1
GND
2
3
Judgment Criteria
Measuring point
Criteria
FG-GND Not less than 1M
Vsp-GND Not less than 100k
Vcc-GND Not less than 100
Vdc-GND Not less than 100k