Daikin REYQ14PY1B [268/477] Push the set bs2 button once to display second digit of malfunction code

Daikin REYQ16PY1B [268/477] Push the set bs2 button once to display second digit of malfunction code
Troubleshooting by Remote Controller SiBE37-701_B
257 Troubleshooting
<Monitor mode>
To enter the monitor mode, push the
MODE (BS1) button when in “Setting
mode 1”.
<Selection of setting item>
* Refer to Page 220 for Monitor mode.
* Refer to Page 220 for Monitor mode.
Push the SET (BS2) button and set
the LED display to a setting item.
<Confirmation of malfunction 1>
Push the RETURN (BS3) button once
to display "First digit" of malfunction
code.
<Confirmation of malfunction 2>
Push the SET (BS2) button once to
display "Second digit" of malfunction
code.
<Confirmation of malfunction 3>
Push the SET (BS2) button once to
display "malfunction location".
<Confirmation of malfunction 4>
Push the SET (BS2) button once to
display "master or slave 1 or slave 2"
and "malfunction location".
Detail
description
on next
page.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
* Push the MODE (BS1) button and
returns to “Setting mode 1”.
Malfunctions Malfunction
code
Description of malfunction Description of malfunction (PGF) Remote
controller
Open phase and unbalanced power
supply
Unbalanced INV power supply voltage P1
INV radiation fin temperature sensor
malfunction
INV fin thermistor malfunction P4
Faulty combination of INV and fan
driver
Faulty combination of INV PJ
Out of gas Out-of-gas alarm U0
Reversed phase Reversed phase malfunction U1
Reversed phase malfunction (ON)
Abnormal power supply voltage Insufficient INV voltage U2
INV open phase (single phase)
Abnormal charge of capacitor of INV
main circuit
Test run not carried out yet Test run not carried out yet U3
Faulty transmission between indoor
and outdoor units
IN-OUT transmission malfunction U4
System malfunction
Faulty transmission between outdoor
units
Malfunction caused when mounting
the external control adaptor
U7
Alarm given when mounting the
external control adaptor
Malfunction caused between the
master and the slave 1
Malfunction caused between the
master and the slave 2
Multi REYQ models connected
Faulty address setting of slaves 1 and 2
4 or more outdoor units connected in
the same system
Erroneous address of slaves 1 and 2
Faulty transmission with other
systems
Other system or other unit in the same
system
U9
Faulty field setting Excess indoor units connected UA
Erroneous refrigerant used for indoor
unit
Faulty combination of outdoor units
Faulty independent installation
Faulty connection of former BS unit
Faulty connection between outdoor
and BS unit
Faulty connection between BS units
Wrong number of indoor units
connected to BS unit
Faulty system line Wrong wiring (auto address error) UH
Faulty transmission with accessory
equipment
Multi level converter malfunction UJ
Multi level converter alarm
Multi level converter data malfunction
Multi level converter transmission
malfunction
Unmatched wiring/piping, no system
settings
Unmatched wiring/piping UF
k
: ON
l
: Blink
h
: OFF