Daikin REYQ14PY1B [332/477] Troubleshooting

Daikin REYQ16PY1B [332/477] Troubleshooting
Troubleshooting by Indication on the Remote Controller SiBE37-701_B
321 Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
YES
Faulty radiation fin from the power
unit
• Blocked suction air port
• Stained radiation fin
• High outdoor temperature
YES
NO
NO
YES
NO
YES
While in monitor mode, check
whether the system is right-
hand (control PCB 1) or left-
hand (control PCB 3).
Individual system
Is the individual
system applied to the
outdoor unit?
Multi system
While in monitor mode,
check the outdoor unit
concerned.
The radiation fin of the inverter
PCB concerned exceeded a
temperature of 87°C.
Turn OFF the power supply,
and then make measurement
of resistance of the radiation
fin thermistor.
Replace the thermistor.
Is the thermistor
resistance normal?
Connect and disconnect
the connector (X111A) for
the fin thermistor, and
then properly connect it.
Does the malfunction
recur when the power
supply turns ON to start
the compressor?
Replace the compressor inverter
PCB.
Continue the operation.
z
It is supposed that the radiation
fin temperature became high due
to some field factors. In this
connection, check the following
points:
Stained radiation fin
Airflow obstructed with dirt or
foreign matters
Damage to fan propellers
Too high outdoor air
temperature