Daikin RXYQ30PAYL [274/452] Troubleshooting

Daikin RXYQ30PAYL [274/452] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si34-803_B
263 Troubleshooting
Troubleshooting
YES
Connect correctly.
YES
Connect correctly.
YES
NO
Remove the foreign matter.
NO
YES
NO
There is a
foreign matter around
the fan.
NO
Replace the fan
PCB (A2P).
Turn off the power and wait for
10 minutes.
YES
NO
Replace the fan motor.
NO
YES
Replace the fan motor.
Remove the power wire
connector from the fan motor
and measure the resistance
between U and V, V and W, and
W and U phases (*1).
A
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The fan
motor connectors (X1A
and X2A) of the fan PCB (A2P) are
disconnected.
The connectors
between the indoor
PCB (A1P) and the fan
PCB (A2P) are
disconnected.
The fuse
(F3U, white) on the fan
PCB (A2P) has no
continuity.
The fan can be
moved lightly by hand after
the fan motor connector of the
fan PCB (A2P) is
removed.
The resistance
between the power wire
terminals of the fan motor and
motor frame (metal part) is
1 M or below.
Continued to the next page.

Содержание

Скачать