Si34-803_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 308
Troubleshooting
A
Power ON
Power OFF
Power OFF
Power ON
NO
NO
NO
YES
YES
YES
YES
YES
NO
NO
Check the compressor motor
coil for any broken wire.
The insulation
resistance is low (i.e.,
not more than
100k.)
Some phase has a
broken wire.
The power
transistor has an
abnormality.
Restart
the compressor, and
then check whether or
not the malfunction
recurs.
Restart
the compressor, and
then check whether or
not the malfunction
recurs.
Replace the compressor.
Replace the inverter PCB
(A3P).
Normal
Onsite causes such as
instantaneous power
failure or open phase
Conduct checks and
diagnosis of the
compressor.
End of work
Replace the compressor.
Conduct checks and
diagnosis of the
compressor.
Check the power transistor on
the inverter PCB using a
multiple tester. [For details,
refer to information in the
"Check for power transistor"
on P.430.
Make wire connections
according to the Wiring Diagram.
Replace the inverter PCB.