Daikin RXYQ30PAYL [324/452] Outdoor unit malfunction of transmission between inverter and control pcb

Daikin RXYQ30PAYL [324/452] Outdoor unit malfunction of transmission between inverter and control pcb
Troubleshooting by Indication on the Remote Controller Si34-803_B
313 Troubleshooting
3.40
LC
Outdoor Unit: Malfunction of Transmission Between
Inverter and Control PCB
Remote
Controller
Display
LC
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Check the communication state between inverter PCB and control PCB by micro-computer.
Malfunction
Decision
Conditions
When the correct communication is not conducted in certain period.
Supposed
Causes
Malfunction of connection between the inverter PCB and outdoor control PCB
Defect of outdoor control PCB (transmission section)
Defect of inverter PCB
Defect of noise filter
Faulty fan inverter
Incorrect type of fan inverter
Faulty compressor
Faulty fan motor