Daikin RXYQ96PATJ [68/108] 4 transmission wiring connection procedure

Daikin RXYQ96PATJ [68/108] 4 transmission wiring connection procedure
EDUS391000-N_a Installation
Installation of Outdoor Units 67
(Refer to figure 17-1)
1. Electric wiring diagram
Printed on the back of the electrical components box lid.
2. Knockout hole
3. Power line
4. Transmission line
(Refer to figure 17-2)
1. Electrical components box lid
2. Service lid
3. [Service precautions] Label location
NOTE
Open the knock holes with a hammer or the like.
After knocking out the holes, we recommend you remove any burrs
and paint them using the repair paint to prevent rusting.
(Refer to figure 17-1, 2)
When passing wiring through the knock holes, remove burrs
around the knock holes and protect the wiring with protective tape.
(Refer to figure 17-1, 2)
If small animals might enter the unit, block off any gaps (hatching
parts in figure 17-1, 2) with material (field supply).
7-4 Transmission Wiring Connection Procedure
Referring to figure 18 connect the transmission wiring between
outside unit and indoor unit, outside unit and outside unit of other
system, outside unit and outside unit of same system.
(Refer to figure 18)
1. Electrical components box (1)
2. Electrical components box (2)
3. Do not open the electrical components box (2) lid.
(There are no work when installation)
4. Never connect the power wire.
5. To outside unit of other system
6.
7. Branch Selector unit
8. Indoor unit
9. Indoor unit (Cooling only)
NOTE
Do not connect the power wiring to terminals for the transmission
wiring. Doing so would destroy the entire system.
When connecting wires to the terminal block on the PC-board, too
much heat or tightening could damage the PC-board. Attach with
care.
See the table below for the tightening torque of the transmission wir-
ing terminals.
Transmission wiring (About the symbol ~ , see figure 18)
should be done within the following limitations.
If they are exceeded, transmission problems may occur.
Between outside unit and Branch Selector (or indoor) unit
Between Branch Selector unit and indoor unit
Between outside unit and outside unit of other systems
Max. wiring length : 3280 ft
Max. total wiring length : 6560 ft
Max. no. of branches : 16
[Note]
No branch is allowed after branch (See figure 19)
Max. no. of outside units of other system
that can be connected : 10
(Refer to figure 19)
1. Branch
2. Branch after branch
Between outside unit and outside unit of same system
Max. wiring length : 100 ft
The transmission wiring inside the electrical components box
should be secured using the clamp (1) as shown in figure 20.
(Refer to figure 20)
1. In the electrical components box
2. Retain to the electrical components box with the acces-
sory clamp (1).
3. Vinyl tube (accessory)
Outside the units, the transmission wiring must be finished simul-
taneously with the local refrigerant piping, and wound with tape
(field supply) as shown in figure 21.
(Refer to figure 21)
1. Suction gas pipe
2. HP/LP gas pipe
3. Liquid pipe
4. Insulation material
5. Finishing tape
6. Transmission wiring
Wiring to other systems should be connected to terminals F1 and
F2 (TO OUT/D UNIT) on the PC-board of the electrical compo-
nents box(1).
7-5 Power Wiring Connection Procedure
Be sure to connect the power supply wiring to the power supply
terminal block and hold it in place using the included clamp as
shown in the figure 22.
The L1, L2, L3 and N phases of the power wiring should be
secured separately to the hook using the included clamp (1).
The ground wiring should be bound to the power wiring using the
included clamp (1) to prevent outside force from being applied to
the terminal area.
(Refer to figure 22)
1. Power supply
(MODEL PAYD:3~460V 60Hz)
(MODEL PATJ:3~208-230V 60Hz)
2. Ground leakage circuit breaker
3. Branch switch, ground leakage circuit breaker
4. Ground wire
5. Electrical components box (1)
6. Electrical components box(2)
7. Do not open the electrical components box (2) lid.
(There are no work when installation)
8. Attach insulation sleeves
9. Power supply terminal block
10. Ground terminal
11. Clamp (1) (accessory)
12. Vinyl tube (accessory)
CAUTION
Be sure to use crimp-style terminal with insulating sleeves for
connections. (See the figure below.)
For wiring, use the designated power wire and connect firmly, then
secure to prevent outside pressure being exerted on the terminal
board.
Use an appropriate screwdriver for tightening the terminal screws.
A screwdriver with a small head will strip the head and make
proper tightening impossible.
Over-tightening the terminal screws may break them.
See the following table for the tightening torque of the terminal
screws.
Screw size Tightening torque (ft · lbf)
M3.5 (A1P) 0.59 ~ 0.71
1
2
1
2
Screw size Tightening torque (ft · lbf)
M8 Power terminal, ground terminal 4.06 ~ 5.38
Power wire
Crimp-style terminal
Insulating sleeve

Содержание

Скачать