Troubleshooting by Remote Controller Si341009
141 Troubleshooting
Troubleshooting
Note:
*1. Check the low pressure value by using pressure gauge in operation.
*2. Compare the actual measurement value by pressure sensor with the value by the pressure
gauge.
*3. Compare the thermistor resistance value with the value on the surface thermometer.
Refer to P.171
Refer to P.172
Is the
temperature difference
between the suction pipe and the
heat exchanger 20 ˚C or
more?
Are the property of
suction pipe thermistor (R8T)
and heat exchanger thermistor
(R9T) normal?
(*3)
Is the
low pressure 0.1MPa
or less? (*1)
Is the
characteristics of low
pressure sensor
normal? (*2)
Replace the low pressure
sensor.
Replace the outdoor unit
main PCB (A1P).
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NONO
YES YES
Remove the factor of
decreasing low pressure.
CHECK 2
Remove the factor of
superheating.
CHECK 3
Replace the thermistor.
Replace the outdoor unit main
PCB (A1P).
NONO
YES
Reset the operation using the remote controller then restart.
Mount a pressure gauge at the service port on the low
pressure side.
Reset the operation using the remote controller then restart.
In heating
In cooling
CHECK 2
CHECK 3