Symptom-based Troubleshooting Si341009
85 Troubleshooting
7 The system
conducts fan
operation but not
cooling or
heating
operation.
This symptom occurs
immediately after turning ON
the power supply.
The system is in preparation
mode of operation.
Wait for a period of approximately
10 minutes.
"UNDER CENTRALIZED
CONTROL" is displayed on the
remote controller and the
cooling/heating operation
stops. The operation switches
to the air supply operation.
Even though, the cooling or
heating operation is set, the air
supply operation continues during
thermal storage operation.
"UNDER CENTRALIZED
CONTROL" is displayed on the
remote controller.
Normal operation.
8 The airflow rate
is not
reproduced
according to the
setting.
Even pressing the AIRFLOW
RATE SET button makes no
changes in the airflow rate.
In heating operation, when the
room temperature reaches the set
degree, the outdoor unit will stop
while the indoor unit is brought to
fan LL operation so that no one
gets cold air.
Furthermore, if fan operation
mode is selected when other
indoor unit is in heating operation,
the system will be brought to fan
LL operation.
Normal operation.
9 The airflow
direction is not
reproduced
according to the
setting.
The airflow direction is not
corresponding to that
displayed on the remote
controller.
The flap does not swing.
Automatic control Normal operation.
10 A white mist
comes out from
the system.
<Indoor unit>
In cooling operation, the
ambient humidity is high.
(This indoor unit is installed in
a place with much oil or dust.)
Uneven temperature distribution
due to heavy stain of the inside of
the indoor unit
Clean the inside of the indoor unit.
<Indoor unit>
Immediately after cooling
operation stopping, the
ambient temperature and
humidity are low.
Hot gas (refrigerant) flown in the
indoor unit results to be vapor
from the unit.
Normal operation.
<Indoor and outdoor units>
After the completion of
defrosting operation, the
system is switched to heating
operation.
Defrosted moisture turns to be
vapor and comes out from the
units.
Normal operation.