Daikin FTX50GV1B [30/131] Fan speed control for indoor unit

Daikin FTX50GV1B [30/131] Fan speed control for indoor unit
Main Functions SiBE041029_A
20 Function and Control
1.4 Fan Speed Control for Indoor Unit
Outline Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H, and HH.
The airflow rate can be automatically controlled depending on the difference between the room
thermistor temperature and the target temperature. This is done through phase control and Hall
IC control.
For more information about Hall IC, refer to the troubleshooting for fan motor on page 59.
Automatic Fan
Speed Control
In automatic fan speed operation, the step “SL” is not available.
= The airflow rate is automatically controlled within this range when the [FAN] setting
button is set to automatic
.
<Cooling>
The following drawing explains the principle of fan speed control for cooling.
<Heating>
In heating operation, the fan speed is regulated according to the indoor heat exchanger
temperature and the difference between the room thermistor temperature and the target
temperature.
Note: 1. During POWERFUL operation, the fan rotates at H tap + 90 rpm.
2. The fan stops during defrost control.
Step Cooling Heating
LLL
LL
L
ML
M
MH
H
HH (POWERFUL)
(R6833)
(R6834)
Room thermistor temperature – target temperature
+1.5˚C
+0.5˚C
+2˚C
+1˚C
M
ML
L
Fan speed
(R12390)

Содержание

Скачать
Случайные обсуждения