SiBE041029_A Troubleshooting
Service Diagnosis 71
Troubleshooting RX50/60G3V1B
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
YES
(R16380)
YES
NO
NO
Replace the outdoor unit
PCB (2).
Ground the system.
Zero-cross signal
abnormality.
Replace the outdoor unit
PCB (1).
Replace the harness.
Check to see if the outdoor unit is
grounded.
Is LED A blinking?
Grounded?
Is the harness
broken?
Turn on the power again.