Control Specification Si12-308A
104 Function and Control
3.12.11Control when frequency is changed
When the target pipe temperature control is active, if the target frequency is changed for a
specified value in a certain time period, cancel the target discharge pipe temperature control
and change the opening of the target electronic expansion valve according to the shift.