Daikin RZQG71L9V1B [100/215] 3 connect a refrigerant recovery unit to perform refrigerant recovery 4 upon completion of refrigerant recovery turn off refrigerant recovery mode by taking the following steps or turning off the power of outdoor unit

Daikin RZQG100L9V1B [100/215] 3 connect a refrigerant recovery unit to perform refrigerant recovery 4 upon completion of refrigerant recovery turn off refrigerant recovery mode by taking the following steps or turning off the power of outdoor unit
Field Setting from Outdoor Unit PCB ESIE15-13C
86 Field Setting
Setting of Refrigerant Recovery Mode
When a refrigerant recovery unit is connected onsite to recover refrigerant, fully open the
expansion valve of the outdoor unit to help the recovery.
(1) Stop operation.
(2) Turn ON refrigerant recovery mode by performing the following steps.
(3) Connect a refrigerant recovery unit to perform refrigerant recovery.
(4) Upon completion of refrigerant recovery, turn OFF refrigerant recovery mode by taking the
following steps or turning OFF the power of outdoor unit.
Note: *1: If you become unsure how many times you have pushed the button, push the MODE (BS1)
button once to return to "Setting mode 1" and start the operating procedure all over again.
h: OFF l: BLINK k: ON
Operating procedure
H1PH2PH3PH4PH5PH6PH7P
Press the MODE (BS1) button of "Setting mode 1" for 5 seconds or more
and set to "Setting mode 2."
khhhhhh
Press the SET (BS2) button 28 times to set the LED display as shown in
the table on the right. (*1)
khkkkhh
Press the RETURN (BS3) button once. (Present settings are displayed.) khhhhhl
Press the SET (BS2) button once to set the LED display as shown in the
table on the right.
khhhhlh
Press the RETURN (BS3) button once to make a decision. khhhhkh
When the RETURN (BS3) button is pressed once again, the electronic
expansion valve opens fully.
khhhhhh
Operating procedure
H1PH2PH3PH4PH5PH6PH7P
Press the SET (BS2) button 28 times to set the LED display as shown in
the table on the right. (*1)
khkkkhh
Press the RETURN (BS3) button once. (Present settings are displayed.) khhhhlh
Press the SET (BS2) button once to set the LED display as shown in the
table on the right.
khhhhhl
Press the RETURN (BS3) button once to make a decision. khhhhhk
When the RETURN (BS3) button is pressed once again, the electronic
expansion valve fully opens.
khhhhhh

Содержание

Скачать