Daikin 2MXS50H2V1B [12/32] Capacity tables

Daikin 2MXS40H2V1B [12/32] Capacity tables
Outdoor Unit • Multi model application • MXS-H
Split - Sky Air
®
• Outdoor Unit
10
4 Capacity tables
4 - 3 Cooling Capacity Tables
2MXS40H2V1B
Cooling (50Hz 230V)
Combination
(Capacity)
Outdoor air
temp.
°CDB
Indoor air temperature: °CWB
14°C 16°C 18°C 19°C 22°C 24°C
TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW
2.5 + 2.5
10.0 4.92 0.88 5.12 0.90 5.32 0.92 5.42 0.93 5.73 0.96 5.93 0.98
12.0 4.84 0.90 5.04 0.92 5.24 0.94 5.34 0.95 5.65 0.98 5.85 1.00
15.0 4.71 0.93 4.92 0.95 5.12 0.97 5.22 0.98 5.52 1.01 5.73 1.03
18.0 4.59 0.97 4.79 0.99 5.00 1.00 5.10 1.01 5.40 1.04 5.60 1.06
20.0 4.51 0.99 4.71 1.01 4.91 1.03 5.01 1.04 5.32 1.07 5.52 1.09
22.0 4.43 1.01 4.63 1.03 4.83 1.05 4.93 1.06 5.24 1.09 5.44 1.11
25.0 4.30 1.05 4.51 1.07 4.71 1.09 4.81 1.10 5.11 1.13 5.32 1.15
28.0 4.18 1.09 4.38 1.11 4.59 1.12 4.69 1.13 4.99 1.16 5.19 1.18
32.0 4.02 1.14 4.22 1.16 4.42 1.18
4.52 1.19
4.83 1.22 5.03 1.24
35.0 3.89 1.18 4.10 1.20 4.30 1.22 4.40 1.23 4.70 1.26 4.91 1.28
40.0 3.69 1.26 3.89 1.28 4.09 1.30
4.20 1.31
4.50 1.34 4.70 1.36
43.0 3.57 1.31 3.77 1.33 3.97 1.34 4.07 1.35 4.38 1.38 4.58 1.40
46.0 3.35 1.30 3.51 1.30 3.67 1.30 3.74 1.30 3.97 1.30 4.11 1.30
2.5 + 3.5
10.0 5.14 0.94 5.35 0.96 5.56 0.98 5.67 0.99 5.99 1.03 6.20 1.05
12.0 5.06 0.96 5.27 0.98 5.48 1.00 5.59 1.01 5.90 1.05 6.12 1.07
15.0 4.93 0.99 5.14 1.02 5.35 1.04 5.46 1.05 5.77 1.08 5.99 1.10
18.0 4.80 1.03 5.01 1.05 5.22 1.07 5.33 1.08 5.65 1.11 5.86 1.13
20.0 4.71 1.05 4.92 1.07 5.14 1.09 5.24 1.10 5.56 1.14 5.77 1.16
22.0 4.63 1.08 4.84 1.10 5.05 1.12 5.16 1.13 5.47 1.16 5.69 1.18
25.0 4.50 1.12 4.71 1.14 4.92 1.16 5.03 1.17 5.35 1.20 5.56 1.22
28.0 4.37 1.16 4.58 1.18 4.79 1.20 4.90 1.21 5.22 1.24 5.43 1.26
32.0 4.20 1.21 4.41 1.23 4.62 1.26
4.73 1.27
5.05 1.30 5.26 1.32
35.0 4.07 1.26 4.28 1.28 4.49 1.30 4.60 1.31 4.92 1.34 5.13 1.36
40.0 3.86 1.34 4.07 1.36 4.28 1.38
4.39 1.39
4.70 1.42 4.92 1.44
43.0 3.73 1.39 3.94 1.41 4.15 1.43 4.26 1.44 4.58 1.47 4.79 1.50
46.0 3.36 1.30 3.52 1.36 3.67 1.30 3.75 1.30 3.97 1.30 4.11 1.30
3D063429A
NOTES SYMBOLS
1 Capacities are based on the following conditions.
Corresponding refrigerant piping length: 5.0m
Level difference: 0m
2 The bold line is indicated the standard condition.
3 The above is the value for connecting with the following indoor units.
2.0, 2.5, 3.5 kW class; wall mounted ATXS-G, FTXS-J (NW-S2)series.
TC: Total capacity (kW)
PI: Power input (kW)

Содержание