Daikin 2MXS50H2V1B [21/32] Capacity tables

Daikin 2MXS40H2V1B [21/32] Capacity tables
Split - Sky Air
®
• Outdoor Unit
19
Outdoor Unit • Multi model application • MXS-H
4 Capacity tables
4 - 4 Heating Capacity Tables
2MXS40H2V1B
Heating (50Hz 230V)
Combination
(Capacity)
Outdoor air
temp.
°CWB
Indoor air temperature: °CDB
16°C 18°C 20°C 21°C 22°C 24°C
TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW
2.0
-10.0 2.47 1.08 2.41 1.09 2.36 1.10 2.34 1.11 2.31 1.11 2.26 1.13
-7.0 2.72 1.11 2.66 1.12 2.61 1.13 2.59 1.14 2.56 1.15 2.51 1.16
-5.0 2.88 1.13 2.83 1.14 2.78 1.15 2.76 1.16 2.73 1.17 2.68 1.18
-2.0 3.13 1.16 3.08 1.17 3.03 1.19 3.01 1.19 2.98 1.20 2.93 1.21
0.0 3.30 1.18 3.25 1.20 3.20 1.21 3.17 1.21 3.15 1.22 3.10 1.23
1.0 3.38 1.19 3.33 1.21 3.28 1.22 3.26 1.22 3.23 1.23 3.18 1.24
3.0 3.55 1.22 3.50 1.23
3.45 1.24
3.42 1.24 3.40 1.25 3.35 1.26
6.0 3.80 1.25 3.75 1.26 3.70 1.27 3.67 1.28 3.65 1.28 3.60 1.29
8.0 3.97 1.27 3.92 1.28
3.87 1.29
3.84 1.30 3.82 1.30 3.76 1.31
10.0 4.14 1.29 4.09 1.30 4.03 1.31 4.01 1.32 3.98 1.32 3.93 1.33
12.0 4.30 1.31 4.25 1.32 4.20 1.33 4.18 1.34 4.15 1.34 4.10 1.36
15.0 4.55 1.34 4.50 1.35 4.45 1.36 4.43 1.37 4.40 1.38 4.35 1.39
18.0 3.93 1.07 3.87 1.07 3.80 1.07 3.77 1.07 3.74 1.07 3.68 1.07
2.5
-10.0 2.73 1.29 2.68 1.31 2.62 1.32 2.59 1.33 2.56 1.33 2.51 1.35
-7.0 3.01 1.33 2.95 1.34 2.90 1.36 2.87 1.36 2.84 1.37 2.78 1.38
-5.0 3.19 1.35 3.14 1.37 3.08 1.38 3.05 1.39 3.02 1.40 2.97 1.41
-2.0 3.47 1.39 3.42 1.41 3.36 1.42 3.33 1.43 3.30 1.43 3.25 1.45
0.0 3.66 1.42 3.60 1.43 3.54 1.44 3.52 1.45 3.49 1.46 3.43 1.47
1.0 3.75 1.43 3.69 1.44 3.64 1.46 3.61 1.46 3.58 1.47 3.52 1.48
3.0 3.94 1.46 3.88 1.47
3.82 1.48
3.79 1.49 3.77 1.50 3.71 1.51
6.0 4.21 1.49 4.16 1.51 4.10 1.52 4.07 1.53 4.04 1.53 3.99 1.55
8.0 4.40 1.52 4.34 1.53
4.29 1.55
4.26 1.55 4.23 1.56 4.17 1.57
10.0 4.58 1.54 4.53 1.56 4.47 1.57 4.44 1.58 4.41 1.58 4.36 1.60
12.0 4.77 1.57 4.71 1.58 4.66 1.60 4.63 1.60 4.60 1.61 4.54 1.62
15.0 4.85 1.52 4.77 1.52 4.69 1.52 4.65 1.52 4.61 1.52 4.54 1.52
18.0 3.81 1.07 3.76 1.07 3.70 1.07 3.67 1.07 3.64 1.07 3.59 1.07
3.5
-10.0 2.93 1.47 2.87 1.49 2.81 1.50 2.78 1.51 2.75 1.52 2.69 1.53
-7.0 3.23 1.51 3.17 1.53 3.11 1.54 3.08 1.55 3.05 1.56 2.99 1.58
-5.0 3.43 1.54 3.37 1.56 3.31 1.57 3.28 1.58 3.25 1.59 3.19 1.60
-2.0 3.73 1.58 3.67 1.60 3.61 1.62 3.57 1.62 3.54 1.63 3.48 1.65
0.0 3.93 1.61 3.86 1.63 3.80 1.64 3.77 1.65 3.74 1.66 3.68 1.68
1.0 4.02 1.63 3.96 1.64 3.90 1.66 3.87 1.67 3.84 1.67 3.78 1.69
3.0 4.22 1.66 4.16 1.67
4.10 1.69
4.07 1.70 4.04 1.70 3.98 1.72
6.0 4.52 1.70 4.46 1.71 4.40 1.73 4.37 1.74 4.34 1.75 4.28 1.76
8.0 4.72 1.73 4.66 1.74
4.60 1.76
4.57 1.77 4.54 1.77 4.48 1.79
10.0 4.92 1.76 4.86 1.77 4.80 1.79 4.77 1.79 4.74 1.80 4.68 1.82
12.0 5.12 1.78 5.06 1.80 5.00 1.82 4.97 1.82 4.94 1.83 4.74 1.76
15.0 4.77 1.52 4.70 1.52 4.62 1.52 4.59 1.52 4.55 1.52 4.48 1.52
18.0 3.75 1.07 3.70 1.07 3.65 1.07 3.62 1.07 3.60 1.07 3.55 1.07
Combination
(Capacity)
Outdoor air
temp.
°CWB
Indoor air temperature: °CDB
16°C 18°C 20°C 21°C 22°C 24°C
TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW
2.0 + 2.0
-10.0 3.06 0.99 3.00 1.01 2.94 1.02 2.91 1.02 2.87 1.03 2.81 1.04
-7.0 3.38 1.02 3.31 1.03 3.25 1.04 3.22 1.05 3.19 1.06 3.12 1.07
-5.0 3.58 1.04 3.52 1.05 3.46 1.06 3.43 1.07 3.39 1.07 3.33 1.09
-2.0 3.90 1.07 3.83 1.08 3.77 1.09 3.74 1.10 3.71 1.10 3.64 1.11
0.0 4.10 1.09 4.04 1.10 3.98 1.11 3.94 1.12 3.91 1.12 3.85 1.13
1.0 4.21 1.10 4.14 1.11 4.08 1.12 4.05 1.13 4.02 1.13 3.95 1.14
3.0 4.42 1.12 4.35 1.13
4.29 1.14
4.26 1.15 4.22 1.15 4.16 1.16
6.0 4.73 1.15 4.66 1.16 4.60 1.17 4.57 1.18 4.54 1.18 4.47 1.19
8.0 4.93 1.17 4.87 1.18
4.81 1.19
4.78 1.19 4.74 1.20 4.68 1.21
10.0 5.14 1.19 5.08 1.20 5.02 1.21 4.98 1.21 4.95 1.22 4.89 1.23
12.0 5.35 1.21 5.29 1.22 5.22 1.23 5.19 1.23 5.16 1.24 5.10 1.25
15.0 5.66 1.24 5.60 1.25 5.53 1.26 5.50 1.26 5.47 1.27 5.41 1.28
18.0 5.17 1.07 5.09 1.07 5.00 1.07 4.95 1.07 4.91 1.07 4.83 1.07
2.0 + 2.5
-10.0 3.13 1.03 3.07 1.04 3.00 1.05 2.97 1.06 2.94 1.06 2.87 1.07
-7.0 3.45 1.06 3.39 1.07 3.32 1.08 3.29 1.09 3.26 1.09 3.19 1.10
-5.0 3.66 1.08 3.60 1.09 3.53 1.10 3.50 1.11 3.47 1.11 3.40 1.12
-2.0 3.98 1.11 3.92 1.12 3.85 1.13 3.82 1.14 3.79 1.14 3.72 1.15
0.0 4.19 1.13 4.13 1.14 4.06 1.15 4.03 1.16 4.00 1.16 3.93 1.17
1.0 4.30 1.14 4.23 1.15 4.17 1.16 4.14 1.17 4.10 1.17 4.04 1.18
3.0 4.51 1.16 4.45 1.17
4.38 1.18
4.35 1.19 4.32 1.19 4.25 1.20
6.0 4.83 1.19 4.76 1.20 4.70 1.21 4.67 1.22 4.64 1.22 4.57 1.23
8.0 5.04 1.21 4.98 1.22
4.91 1.23
4.88 1.24 4.85 1.24 4.78 1.25
10.0 5.25 1.23 5.19 1.24 5.12 1.25 5.09 1.26 5.06 1.26 4.99 1.27
12.0 5.47 1.25 5.40 1.26 5.34 1.27 5.30 1.28 5.27 1.28 5.21 1.29
15.0 5.79 1.28 5.72 1.29 5.66 1.30 5.62 1.31 5.59 1.31 5.53 1.32
18.0 5.14 1.07 5.05 1.07 4.97 1.07 4.92 1.07 4.88 1.07 4.80 1.07
2.0 + 3.5
-10.0 3.13 1.01 3.07 1.02 3.00 1.03 2.97 1.04 2.94 1.04 2.87 1.05
-7.0 3.45 1.04 3.39 1.05 3.32 1.06 3.29 1.07 3.26 1.07 3.19 1.08
-5.0 3.66 1.06 3.60 1.07 3.53 1.08 3.50 1.09 3.47 1.09 3.40 1.10
-2.0 3.98 1.09 3.92 1.10 3.85 1.11 3.82 1.12 3.79 1.12 3.72 1.13
0.0 4.19 1.11 4.13 1.12 4.06 1.13 4.03 1.14 4.00 1.14 3.93 1.15
1.0 4.30 1.12 4.23 1.13 4.17 1.14 4.14 1.15 4.10 1.15 4.04 1.16
3.0 4.51 1.14 4.45 1.15
4.38 1.16
4.35 1.17 4.32 1.17 4.25 1.18
6.0 4.83 1.17 4.76 1.18 4.70 1.19 4.67 1.20 4.64 1.20 4.57 1.21
8.0 5.04 1.19 4.98 1.20
4.91 1.21
4.88 1.21 4.85 1.22 4.78 1.23
10.0 5.25 1.21 5.19 1.22 5.12 1.23 5.09 1.23 5.06 1.24 4.99 1.25
12.0 5.47 1.23 5.40 1.24 5.34 1.25 5.30 1.25 5.27 1.26 5.21 1.27
15.0 5.79 1.26 5.72 1.27 5.66 1.28 5.62 1.28 5.59 1.29 5.53 1.30
18.0 5.21 1.07 5.12 1.07 5.03 1.07 4.99 1.07 4.95 1.07 4.86 1.07
3D063457A
NOTES SYMBOLS
1 Capacities are based on the following conditions.
Corresponding refrigerant piping length: 5.0m
Level difference: 0m
2 The bold line is indicated the standard condition.
3 The above is the value for connecting with the following indoor units.
2.0, 2.5, 3.5 kW class; wall mounted ATX-G, ATX-J (GSI-S)series.
TC: Total capacity (kW)
PI: Power input (kW)

Содержание