Daikin 2MXS50H2V1B [18/32] Capacity tables

Daikin 2MXS50H2V1B [18/32] Capacity tables
Outdoor Unit • Multi model application • MXS-H
Split - Sky Air
®
• Outdoor Unit
16
4 Capacity tables
4 - 3 Cooling Capacity Tables
2MXS50
Cooling (50Hz 230V)
3D059194
Combination
(Capacity)
outdoor
air temp.
Indoor air temp.: °CWB
14.0°C 16.0°C 18.0°C 19.0°C 22.0°C 24.0°C
TC PI TC PI TC PI TC PI TC PI TC PI
°CDBkWkWkWkWkWkWkWkWkWkWkWkW
2.5+4.2 10.0 6.04 1.30 6.28 1.32 6.53 1.35 6.66 1.37 7.03 1.41 7.28 1.44
12.0 5.93 1.32 6.18 1.35 6.43 1.38 6.56 1.39 6.93 1.44 7.18 1.47
15.0 5.78 1.37 6.03 1.40 6.28 1.42 6.41 1.44 6.78 1.48 7.03 1.51
18.0 5.63 1.41 5.88 1.44 6.13 1.47 6.25 1.48 6.63 1.53 6.88 1.56
20.0 5.53 1.45 5.78 1.47 6.03 1.50 6.15 1.52 6.53 1.56 6.78 1.59
22.0 5.43 1.48 5368 1.51 5.93 1.54 6.05 1.55 6.43 1.59 6.68 1.62
25.0 5.28 1.53 5.53 1.56 5.78 1.59 5.90 1.60 6.28 1.65 6.52 1.68
28.0 5.13 1.59 5.38 1.62 5.63 1.65 5.75 1.66 6.13 1.70 6.37 1.73
32.0 4.93 1.67 5.18 1.70 5.43 1.72 5.55 1.74 5.92 1.78 6.17 1.81
35.0 4.78 1.73 5.03 1.76 5.28 1.79 5.40 1.80 5.77 1.85 6.02 1.87
40.0 4.53 1.84 4.78 1.87 5.02 1.90 5.15 1.91 5.52 1.96 5.77 1.98
43.0 4.38 1.91 4.62 1.94 4.87 1.97 5.00 1.98 5.37 2.03 5.62 2.05
46.0 4.22 1.98 4.47 2.01 4.72 2.04 4.85 2.06 5.22 2.10 5.47 2.13
2.5+5.0 10.0 6.04 1.24 6.28 1.27 6.53 1.30 6.66 1.31 7.03 1.36 7.28 1.41
12.0 5.93 1.27 6.18 1.30 6.43 1.33 6.56 1.34 6.93 1.38 7.18 1.41
15.0 5.78 1.31 6.03 1.34 6.28 1.37 6.41 1.38 6.78 1.42 7.03 1.45
18.0 5.63 1.36 5.88 1.39 6.13 1.41 6.25 1.43 6.63 1.47 6.88 1.50
20.0 5.53 1.39 5.78 1.42 6.03 1.44 6.15 1.46 6.53 1.50 6.78 1.53
22.0 5.43 1.42 5.68 1.45 5.93 1.48 6.05 1.49 6.43 1.53 6.68 1.56
25.0 5.28 1.47 5.53 1.50 5.78 1.53 5.90 1.54 6.28 1.58 6.52 1.61
28.0 5.13 1.53 5.38 1.55 5.63 1.58 5.75 1.60 6.13 1.64 6.37 1.66
32.0 4.93 1.60 5.18 1.63 5.43 1.66 5.55 1.67 5.92 1.71 6.17 1.74
35.0 4.78 1.66 5.03 1.69 5.28 1.72 5.40 1.73 5.77 1.77 6.02 1.80
40.0 4.53 1.77 4.78 1.08 5.02 1.82 5.15 1.84 5.52 1.88 5.77 1.91
43.0 4.38 1.84 4.62 1.86 4.87 1.89 5.00 1.91 5.37 1.95 5.62 1.97
46.0 4.22 1.91 4.47 1.93 4.72 1.96 4.85 1.98 5.22 2.02 5.47 2.04
3.5+3.5 10.0 5.92 1.24 6.17 1.27 6.41 1.29 6.53 1.31 6.90 1.35 7.14 1.38
12.0 5.82 1.26 6.07 1.29 6.31 1.32 6.44 1.33 6.80 1.37 7.05 1.40
15.0 5.68 1.31 5.92 1.33 6.17 1.36 6.29 1.37 6.65 1.42 6.90 1.44
18.0 5.53 1.35 5.77 1.38 6.02 1.41 6.14 1.42 6.51 1.46 6.75 1.49
20.0 5.43 1.38 5.67 1.41 5.92 1.44 6.04 1.45 6.41 1.49 6.65 1.52
22.0 5.33 1.41 5.58 1.44 5.82 1.47 5.94 1.48 6.31 1.52 6.55 1.55
25.0 5.18 1.46 5.43 1.49 5.67 1.52 5.79 1.53 6.16 1.57 6.40 1.60
28.0 5.04 1.52 5.28 1.55 5.52 1.57 5.65 1.59 6.01 1.63 6.26 1.66
32.0 4.84 1.59 5.08 1.62 5.33 1.65 5.45 1.66 5.81 1.70 6.06 1.73
35.0 4.69 1.65 4.93 1.68 5.18 1.71 5.30 1.72 5.67 1.76 5.91 1.79
40.0 4.44 1.76 4.69 1.79 4.93 1.81 5.05 1.83 5.42 1.87 5.66 1.90
43.0 4.29 1.83 4.54 1.85 4.78 1.88 4.91 1.89 5.27 1.94 5.52 1.96
46.0 4.15 1.90 4.39 1.92 4.63 1.95 4.76 1.96 5.12 2.01 5.37 2.03
Combination
(Capacity)
outdoor
air temp.
Indoor air temp.: °CWB
14.0°C 16.0°C 18.0°C 19.0°C 22.0°C 24.0°C
TC PI TC PI TC PI TC PI TC PI TC PI
°CDBkWkWkWkWkWkWkWkWkWkWkWkW
3.5+4.2 10.0 6.04 1.27 6.28 1.30 6.53 1.33 6.66 1.34 7.03 1.39 7.28 1.42
12.0 5.93 1.30 6.18 1.33 6.43 1.36 6.56 1.37 6.93 1.41 7.18 1.44
15.0 5.78 1.34 6.03 1.37 6.28 1.40 6.41 1.41 6.78 1.46 7.03 1.49
18.0 5.63 1.39 5.88 1.42 6.13 1.45 6.25 1.46 6.63 1.50 6.88 1.53
20.0 5.53 1.42 5.78 1.45 6.03 1.48 6.15 1.49 6.53 1.53 6.78 1.56
22.0 5.43 1.45 5.68 1.48 5.93 1.51 6.05 1.53 6.43 1.57 6.68 1.60
25.0 5.28 1.51 5.53 1.54 5.78 1.56 5.90 1.58 6.28 1.62 6.52 1.65
28.0 5.13 1.56 5.38 1.59 5.63 1.62 5.75 1.63 6.13 1.68 6.37 1.70
32.0 4.93 1.64 5.18 1.67 5.43 1.70 5.55 1.71 5.92 1.75 6.17 1.78
35.0 4.78 1.70 5.03 1.73 5.28 1.76 5.40 1.77 5.77 1.81 6.02 1.84
40.0 4.53 1.81 4.78 1.84 5.02 1.87 5.15 1.88 5.52 1.92 5.77 1.95
43.0 4.38 1.88 4.62 1.91 4.87 1.94 5.00 1.95 5.37 1.99 5.62 2.02
46.0 4.22 1.95 4.47 1.98 4.72 2.01 4.85 2.02 5.22 2.06 5.47 2.09
3.5 10.0 6.04 1.22 6.28 1.25 6.53 1.28 6.66 1.29 7.03 1.33 7.28 1.39
12.0 5.93 1.25 6.18 1.28 6.43 1.30 6.56 1.32 6.93 1.36 7.18 1.39
15.0 5.78 1.29 6.03 1.32 6.28 1.34 6.41 1.36 6.78 1.40 7.03 1.43
18.0 5.63 1.33 5.88 1.36 6.13 1.39 6.25 1.40 6.63 1.44 6.88 1.47
20.0 5.53 1.37 5.78 1.39 6.03 1.42 6.15 1.43 6.53 1.47 6.78 1.50
22.0 5.43 1.40 5.68 1.42 5.93 1.45 6.05 1.47 6.43 1.51 6.68 1.53
25.0 5.28 1.45 5.53 1.47 5.78 1.50 5.90 1.52 6.28 1.56 6.52 1.58
28.0 5.13 1.50 5.38 1.53 5.63 1.55 5.75 1.57 6.13 1.63 6.37 1.64
32.0 4.93 1.57 5.18 1.60 5.43 1.63 5.55 1.64 5.92 1.68 6.17 1.71
35.0 4.78 1.63 5.03 1.66 5.28 1.69 5.40 1.70 5.77 1.74 6.02 1.77
40.0 4.53 1.74 4.78 1.77 5.02 1.79 5.15 1.81 5.52 1.85 5.77 1.87
43.0 4.38 1.80 4.62 1.83 4.87 1.86 5.00 1.87 5.37 1.91 5.62 1.94
46.0 4.22 1.87 4.47 1.90 4.72 1.93 4.85 1.94 5.22 1.98 5.47 2.01
3.5+3.5 10.0 6.04 1.24 6.28 1.27 6.53 1.30 6.66 1.31 7.03 1.36 7.28 1.38
12.0 5.93 1.27 6.18 1.30 6.43 1.33 6.56 1.34 6.93 1.38 7.18 1.41
15.0 5.78 1.31 6.03 1.34 6.28 1.37 6.41 1.38 6.78 1.42 7.03 1.45
18.0 5.63 1.36 5.88 1.39 6.13 1.41 6.25 1.43 6.63 1.47 6.88 1.50
20.0 5.53 1.39 5.78 1.42 6.03 1.44 6.15 1.46 6.53 150 6.78 1.53
22.0 5.43 1.42 5.68 1.45 5.93 1.48 6.05 1.49 6.43 1.53 6.68 1.56
25.0 5.28 1.47 5.53 1.50 5.78 1.53 5.90 1.54 6.28 1.58 6.52 1.61
28.0 5.13 1.53 5.38 1.55 5.63 1.58 5.75 1.60 6.13 1.64 6.37 1.66
32.0 4.93 1.60 5.18 1.63 5.43 1.66 5.55 1.67 5.92 1.73 6.17 1.174
35.0 4.78 1.66 5.03 1.69 5.28 1.72 5.40 1.73 5.77 1.77 6.02 1.80
40.0 4.53 1.77 4.78 1.80 5.02 1.82 5.15 1.84 5.52 1.88 5.77 1.91
43.0 4.38 1.84 4.62 1.86 4.87 1.89 5.00 1.91 5.37 1.95 5.62 1.97
46.0 4.22 1.91 4.47 1.93 4.72 1.96 4.85 1.98 5.22 2.02 5.47 2.04
SYMBOLS
TC: Total capacity (kW)
PI: Power input (kW)
NOTES
1 Capacities are based on the following conditions.
Corresponding refrigerant piping length: 5m
Level difference: 0m
2 The bold line is indicated the standard condition.
3 The above is the value for connecting with the following indoor units.
2.0, 2.5, 3.5, 4.2, 5.0 kW Class; wall mounted series.
H
H

Содержание

Скачать