Daikin 2MXS50H2V1B [20/32] Capacity tables

Daikin 2MXS50H2V1B [20/32] Capacity tables
Outdoor Unit • Multi model application • MXS-H
Split - Sky Air
®
• Outdoor Unit
18
4 Capacity tables
4 - 4 Heating Capacity Tables
2MXS40H2V1B
Heating (50Hz 230V)
Combination
(Capacity)
Outdoor air
temp.
°CWB
Indoor air temperature: °CDB
16°C 18°C 20°C 21°C 22°C 24°C
TC PI TC PI TC PI TC PI TC PI TC PI
kW kW kW kW kW kW kW kW kW kW kW kW
2.5 + 2.5
-10.0 3.13 0.99 3.07 1.00 3.00 1.01 2.97 1.01 2.94 1.02 2.87 1.03
-7.0 3.45 1.01 3.39 1.03 3.32 1.04 3.29 1.04 3.26 1.05 3.19 1.06
-5.0 3.66 1.03 3.60 1.04 3.53 1.05 3.50 1.06 3.47 1.07 3.40 1.08
-2.0 3.98 1.06 3.92 1.07 3.85 1.08 3.82 1.09 3.79 1.09 3.72 1.10
0.0 4.19 1.08 4.13 1.09 4.06 1.10 4.03 1.11 4.00 1.11 3.93 1.12
1.0 4.30 1.09 4.23 1.10 4.17 1.11 4.14 1.12 4.10 1.12 4.04 1.13
3.0 4.51 1.11 4.45 1.12
4.38 1.13
4.35 1.14 4.32 1.14 4.25 1.15
6.0 4.83 1.14 4.76 1.15 4.70 1.16 4.67 1.17 4.64 1.17 4.57 1.18
8.0 5.04 1.16 4.98 1.17
4.91 1.18
4.88 1.18 4.85 1.19 4.78 1.20
10.0 5.25 1.18 5.19 1.19 5.12 1.20 5.09 1.20 5.06 1.21 4.99 1.22
12.0 5.47 1.20 5.40 1.21 5.34 1.22 5.30 1.22 5.27 1.23 5.21 1.24
15.0 5.79 1.23 5.72 1.24 5.66 1.25 5.62 1.25 5.59 1.26 5.53 1.27
18.0 5.32 1.07 5.23 1.07 5.14 1.07 5.10 1.07 5.05 1.07 4.96 1.07
2.5 + 3.5
-10.0 3.13 0.94 3.07 0.95 3.00 0.96 2.97 0.97 2.94 0.97 2.87 0.98
-7.0 3.45 0.97 3.39 0.98 3.32 0.99 3.29 1.00 3.26 1.00 3.19 1.01
-5.0 3.66 0.99 3.60 1.00 3.53 1.01 3.50 1.01 3.47 1.02 3.40 1.03
-2.0 3.98 1.02 3.92 1.03 3.85 1.04 3.82 1.04 3.79 1.05 3.72 1.06
0.0 4.19 1.04 4.13 1.05 4.06 1.06 4.03 1.06 4.00 1.07 3.93 1.08
1.0 4.30 1.04 4.23 1.05 4.17 1.06 4.14 1.07 4.10 1.07 4.04 1.08
3.0 4.51 1.06 4.45 1.07
4.38 1.08
4.35 1.09 4.32 1.09 4.25 1.10
6.0 4.83 1.09 4.76 1.10 4.70 1.11 4.67 1.12 4.64 1.12 4.57 1.13
8.0 5.04 1.11 4.98 1.12
4.91 1.13
4.88 1.13 4.85 1.14 4.78 1.15
10.0 5.25 1.13 5.19 1.14 5.12 1.15 5.09 1.15 5.06 1.16 4.99 1.17
12.0 5.47 1.14 5.40 1.15 5.34 1.16 5.30 1.17 5.27 1.17 5.21 1.18
15.0 5.79 1.17 5.72 1.18 5.66 1.19 5.62 1.20 5.59 1.20 5.53 1.21
18.0 5.52 1.07 5.43 1.07 5.33 1.07 5.29 1.07 5.24 1.07 5.15 1.07
3D063431A
NOTES SYMBOLS
1 Capacities are based on the following conditions.
Corresponding refrigerant piping length: 5.0m
Level difference: 0m
2 The bold line is indicated the standard condition.
3 The above is the value for connecting with the following indoor units.
2.0, 2.5, 3.5 kW class; wall mounted ATXS-G, FTXS-J (NW-S2)series.
TC: Total capacity (kW)
PI: Power input (kW)