Daikin 2MXS50H2V1B [7/32] Electrical data

Daikin 2MXS40H2V1B [7/32] Electrical data
Split - Sky Air
®
• Outdoor Unit
5
Outdoor Unit • Multi model application • MXS-H
3 Electrical data
3 - 1 Electrical Data
3D055827B
NOTES
1. RLA is based on the following conditions.
Cooling:
Indoor temperature, 27°C DB/19.0 °C WB
Outdoor temperature, 35°C DB
2. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminal is not below or above listed range limits.
3. Maximum allowable voltage variation between phases is 2%.
4. MCA represents maximum input current.
MFA represents capacity which may accept MCA.
5. Select wire size based on the larger value of MCA.
6. MFA is used to select the circuit breaker and the ground fault
circuit interrupter (earth leakage circuit breaker).
2MXS40H
Model Units Power supply Comp. OFM
Outdoor
H/P
C/O
Hz Volts Min. Max. MCA MFA MSC RLA W FLA
2MXS40H H/P 50
220 198 242
9.0 16
4.9 4.37
40 0.17
230 207 253
4.9 4.39
240 216 264
4.9 4.41
SYMBOLS
MCA : Min. Circuit Amps. (A)
MFA : Max. Fuse Amps. (A)
MSC : Max. current during the Starting compressor. (A)
RLA : Rated Load Amps. (A)
OFM : Outdoor Fan Motor.
FLA : Full Load Amps. (A)
W : Fan Motor Rated Output. (W)
3D057669B
NOTES
1. RLA is based on the following conditions.
Cooling:
Indoor temperature, 27°C DB/19.0 °C WB
Outdoor temperature, 35°C DB
2. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminal is not below or above listed range limits.
3. Maximum allowable voltage variation between phases is 2%.
4. MCA represents maximum input current.
MFA represents capacity which may accept MCA.
5. Select wire size based on the larger value of MCA.
6. MFA is used to select the circuit breaker and the ground fault
circuit interrupter (earth leakage circuit breaker).
2MXS50H
Model Units Power supply Comp. OFM
Outdoor
H/P
C/O
Hz Volts Min. Max. MCA MFA MSC RLA W FLA
2MXS50H H/P 50
220 198 242
10.5 16
6.9 6.34
42 0.18
230 207 253
6.9 6.36
240 216 264
6.9 6.38
SYMBOLS
MCA : Min. Circuit Amps. (A)
MFA : Max. Fuse Amps. (A)
MSC : Max. Starting current
RLA : Rated Load Amps. (A)
OFM : Outdoor Fan Motor
FLA : Full Load Amps. (A)
W : Fan Motor Rated Output (W)