Daikin RKS50BVMB [9/26] Specifications

Daikin RKS50BVMB [9/26] Specifications
ELECTRICAL DATA
RKS+FCQ35B
RKS+FCQ50B
RKS+FCQ60B
* This information was not available at the time of publication.
RKS+FHQ35B
Indoor unit Outdoor unit
Power supply Compressor OFM IFM
Hz-Volts
Voltage range
MCA MFA RHz RLA W FLA W FLA
FHQ35BUV1B RKS35BVMB 50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15 15 78 4.91 19 0.35 62 0.6
3D040596
RKS+FHQ50B
RKS+FHQ60B
Indoor unit Outdoor unit
Power supply Compressor OFM IFM
Hz-Volts
Voltage range
MCA MFA RHz RLA W FLA W FLA
FHQ50BUV1B RKS50BVMB 50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18 20 79 7.5 53 0.18 62 0.6
FHQ60BUV1B RKS60BVMB 50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18 20 90 8.84 53 0.24 62 0.6
3D040597
RKS+FBQ35B
RKS+FBQ50B
RKS+FBQ60B
* This information was not available at the time of publication.
SYMBOLS
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps (A)
RHz : Rated operating frequency (Hz)
RLA : Rated Load Amps (A)
OFM : Outdoor Fan Motor
IFM : Indoor Fan Motor
FLA : Full Load Amps
W : Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
Pair Application R-410A RKS25-35-50-60-71BVMB
2
Specifications
2
7
Split - Sky Air Outdoor Units