Daikin CDX60AVMC [115/302] Control when frequency is changed

Daikin CDK50AVMA [115/302] Control when frequency is changed
Control Specification Si12-308
104 Function and Control
3.12.11Control when frequency is changed
When the target pipe temperature control is active, if the target frequency is changed for a
specified value in a certain time period, cancel the target discharge pipe temperature control
and change the opening of the target electronic expansion valve according to the shift.

Содержание

Скачать