1-19
English
ADDITIONAL CHARGE
The refrigerant is pre-charge in the outdoor unit. If the piping length is less than 7.5m, then additional charge after
vacuuming is not necessary. If the piping length is more than 7.5m then use the additional charge value as indicated in the
table.
Additional refrigerant charge [g] per additional 1m length as tabulated (for R22 models)
Cooling only
Model
Indoor FHC20JEVLK FHC25JEVLK
Outdoor RD20JEVLK RD25JEVLK*
Additional charge [g/m] 22 55
Model
Indoor FHC30JEVLK FHC40JEVLK
Outdoor RD30JEVLK RD40JEVLK
Additional charge [g/m] 57 40
Model
Indoor FHC50JEVLK
Outdoor RD50JETLK
Additional charge [g/m] 58
Heat Pump Unit
Model
Indoor FHYC20JEVLK FHYC25JEVLK
Outdoor RYD20JEVLK RYD25JEVLK*
Additional charge [g/m] 22 55
Model
Indoor FHYC30JEVLK FHYC40JEVLK
Outdoor RYD30JEVLK RYD40JEVLK
Additional charge [g/m] 57 40
Model
Indoor FHYC50JEVLK
Outdoor RYD50JETLK
Additional charge [g/m] 58
Example:
FHC20JEVLK & RD20JEVLK with 13m piping length, additional piping length is 5.5m. Thus,
Additional charge = 5.5[m] x 22[g/m]
= 121[g]
! CAUTION
* When connect with FHC25JEVLK and FHYC25JEVLK, additional 0.2kg refrigerant charge is needed for 3.0m to
7.5m piping length.