Haier AC122ACERA [176/408] Installation

Haier AU48NAIERA [176/408] Installation
Air discharging fan
Improper example
There may be water drop on the outside of duct. For cement and other new constructions, even
if not taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiber
to perform heat preservation to the whole. (use iron net to bind the glass fiber)
Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction,
when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow,
leading to water leakage.
Maybe exceeding the unit operation limit (for example: when indoor dry bulb temperature is 35 C,
wet bulb temperature 24 C), it may lead to overload of comperessor.
(The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause
water leakage.)
The outdoor unit has been charged with refrigerant.
When connecting the pipe to the unit or dismantling the pipe from the unit, please follow the figure
shown, use spanner and torque spanner together.
When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil.
Use hand to twist 3-4 rings, then fasten with spanner.
Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)
Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown.
Only use seal cushion to bind the joint part of air pipe and heat insulation parts.
Paste the refrigerant oil here
Torque spanner
Spanner
Pipe joint
Cone nut
Middle size seal cushion (accessory)
(Use seal cushion to
bind the pipe joint)
Clamp
Heat insulation (accessory)
(for liquid pipe)
(for gas pipe)
Heat insulation (accessory)
Gas pipe
Liquid pipe
11. Refrigerant pipe
Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1) Selection of size of power supply and interconnecting
Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped
terminal lugs with
insulated grip on the ends of the wires.