Haier AC122ACERA [177/408] Installation

Haier AD282AMEAA [177/408] Installation
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with
less than 2% voltage drop.)
(2) Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by
terminals.
AD362ANEAA
AD422ANEAA
AD482ANEAA
AD482ANERA
AD362ANEAA
1PH,220-230V~,50Hz
POWER SUPPLY:
INDOOR UNIT
TERMINAL BLOCK
L N
1 2 3
1 2 3
OUTDOOR UNIT
TERMINAL BLOCK
Y/G
Y/G
Item
Model
Phase
Switch breaker
(A)
Circuit breaker
Overcurrent
protector
Power source
wire size
(minimum)
(mm
2
)
Switch
breaker(A)
Earth leakage breaker
Leak
current(mA)
3 30 20 2.5 30 30
AD422ANEAA
AD482ANEAA
AD482ANERA
301 40 30 6.0 40
AD362ANEAA
3 30 20 4.0 30 30
AD362ANEAA
OUTDOOR UNIT
TERMINAL BLOCK
INDOOR UNIT
TERMINAL BLOCK
POWER SUPPLY:
380-400V, 3N~,50Hz
R S T
N 1 2 3
1 2 3
Y/G
Y/G
Installation
-160-