Aten CC2000 4.0 [161/371] Monitoring settings

Aten CC2000 4.0 [161/371] Monitoring settings
Chapter 5. Device Management
147
Monitoring Settings
You can create monitoring items to observe and record port or equipment
status, such as temperature, humidity, door (open/close), voltage, power
dissipation, current, and to be notified of critical events via e-mail or messages.
Note:
The data size acquired for obtaining the value of a monitored device/port
each time is 8 Bytes. Assuming CC2000 updates readings every 15
seconds, it will take around 4.5 MB a day for 100 monitoring items (100 x
8 x 60/15 x 24 x 60).
The system does not support backup of monitoring data to secondary/
redundant server. To back up monitoring data, create a backup task to
another server. For details, see Backup Primary Server Database,
page 224.
To go to the Monitoring Settings page, go to Device Management >
Monitoring Settings. This page appears.
On the Monitoring Settings page, you can find a list of created monitors,
along with the following information (column):
Value: This is the current value or status for the monitored equipment
Classification: This field indicates the type of the monitored
equipment.
Status: This identifies the general status of the monitored equipment to
be normal, off-line, locked, or warning.
Source: This field indicates the model and IP address of the source
device. Click on the source text (blue) to redirect to the corresponding
device list page.