eco PDU PE Series User Manual
38
(Continues on next page.)
Power On Time Schedule Settings
Check the Enable Power On Time Schedule box to use the Power ON
Delay setting to set the amount of time the eco PDU waits before powering
on an outlet. See Power ON Delay in the table below.
Buzzer Setting
Checking the Enable Buzzer Alarm box sounds an alarm and sends
SNMP trap or e-mail alerts when a circuit breaker trips or a PDU/Outlet
threshold setting exceeds the minimum or maximum setting.
Outlet Configuration
The Outlet Configuration section lets you set the power management
settings for each outlet on the PDU.
Heading Meaning
Outlet Name Each outlet can be given a distinctive name. The maximum
number of characters is 15.
Confirmation
Required
If this option is enabled (there is a check in the checkbox), a dialog
box comes up asking you to confirm a power operation before it is
performed. If it is disabled (there is no check in the checkbox), the
operation is performed without confirmation.
Power ON Delay Sets the amount of time the eco PDU waits after the power button
is clicked (see Outlet Status, page 36), before it turns on the power
to the outlet. You must check the Enable Power On Time Schedule
Setting box for this setting to take effect. See Power On Time
Schedule Settings, page 38, for details.
Note: The default delay time is 0 seconds; the maximum is 999
seconds. When a series of outlets are scheduled to be powered
up, they turn on in sequence with a default delay of 10
milliseconds between each outlet.
Power OFF Delay Sets the amount of time the eco PDU waits after the Power Button
is clicked (see Outlet Status, page 36), before it turns off the power
to the outlet.
For the System after AC Back option (see below), after the delay
time expires, the eco PDU waits another fifteen seconds, then
shuts the computer down.
The default delay time is 15 seconds. The maximum delay time is
999 seconds.