Moxa ioLogik R1210-T [7/64] Specifications

Moxa ioLogik R1241-T [7/64] Specifications
ioLogik R1200 Series Overview
1-3
Specifications
Common Specifications
Serial Communication
Interface:
RS-485-2w: Data+, Data-, GND (5-contact terminal block)
Serial Line Protection:
15 kV ESD for all signals, Level 2 surge, EN 61000-4-5 (1 kV)
Serial Communication Parameters
Parity:
None, Even, Odd (default = None)
Data Bits:
8
Stop Bits:
1, 2 (default = 1)
Baudrate:
1200 to 921.6 kbps (default = 9600)
Pull High/Low Resistor
for RS-485: 1 kΩ, 150 kΩ
Protocols:
Modbus RTU
Physical Characteristics
Wiring:
I/O cable max. 16 AWG
Dimensions:
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Environmental Limits
Operating Temperature:
Standard Models:
-10 to 75°C (14 to 167°F)
Wide Temp. Models:
-40 to 85°C (-40 to 185°F)
Storage Temperature:
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity:
5 to 95% (non-condensing)
Standards and Certifications
Safety:
UL 508
EMI:
EN 55022, EN 61000
-3-2, EN 61000-3-3, FCC Part 15 Subpart B Class A
EMS:
EN 55024, IEC 61000
-4, IEC 61000-6
Shock:
IEC 60068-2-27
Freefall:
IEC 60068-2-32
Vibration:
IEC 60068-2-6
Warranty
Warranty Period:
5 years (excluding the ioLogik R1214)
Details:
See www.moxa.com/warranty