Moxa ioLogik R1210-T [8/64] Iologik r1210

Moxa ioLogik R1214-T [8/64] Iologik r1210
ioLogik R1200 Series Overview
1-4
ioLogik R1210
Inputs and Outputs
Digital Inputs:
16 channels
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to
COM):
• On:
10 to 30 VDC
• Off: 0 to 3 VDC
Common Type:
8 points per COM
Counter Frequency:
2.5 kHz, power off storage
Digital Filtering Time Interval:
Software selectable
Power Requirements
Power Input:
24 VDC nominal, 12 to 48 VDC
Power Consumption:
154 mA @ 24VDC
ioLogik R1212
Inputs and Outputs
Digital Inputs:
8 channels
Configurable DIOs:
8 channels
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short
to GND
• Off: open
Wet Contact (DI to
COM):
• On:
10 to 30 VDC
• Off: 0 to 3 VDC
Common Type:
8 points per COM
Counter Frequency:
2.5 kHz, power off storage
Digital Filtering Time Interval:
Software selectable
Digital Output
Type:
Sink
I/O Mode:
DO or Pulse Output
Pulse Output Frequency:
5 kHz
Over
-voltage Protection: 45 VDC
Over
-current Protection: 2.6 A (4 channels @ 650 mA)
Over
-temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating:
200 mA per channel
Power Requirements
Power Input:
24 VDC nominal, 12 to 48 VDC
Power Consumption:
187 mA @ 24VDC