3-2
Click&Go V2 Development Process
After searching and setting up the IP address of an ioLogik Ethernet I/O server, Click&Go V2 logic can be
developed by following the procedures below:
I/O Configuration
The ioLogik series products are embedded with various types of I/O channels and the mode of each
input/output channel must be configured first. The channels are divided into digital inputs, digital outputs,
analog inputs, analog output, and virtual channels.
Configurable DIO Channel Mode Selection
For the models that support the configurable DIO channels, configure the specific DIO to DI or DO to meet the
requirements.
Model Available
Number of
Configurable DIO
Channels
Mode Selection:
Digital Input
Mode Selection:
Digital Output
ioLogik E2212 4
ioLogik E2242 12
When logged in as an administrator, double click on a channel in the I/O Configuration tab to configure that
channels settings. A window will open with configuration options for that channel. Each DIO channel will be
configured to act as either a DI or DO channel, according to the Power On Settings. To switch between DI and
DO channel operation, select the desired mode in the I/O Direction field under Power On Settings. After
clicking Apply, you will need to restart the ioLogik for the new setting to take effect.
ATTENTION
Before
performing any further configuration or programming, switching between DI and DO channel
requires
restarting the ioLogik for the new setting to take effect.