Input Module (ioLogik E2242 192.168.127.154)
I/O Configuration:
The DIO-0 to DIO-5 is configured as a digital input and displayed as DI-0 to DI-5 in the Click&GO settings tab.
The DIO-6 to DIO-11 is configured as a digital output and displayed as DO-6 to DO-11 in the Click&GO settings
tab.
Rule 0: Send I/O status to 192.168.127.3
1. In ioAdmin, make sure that you have searched for and selected the correct ioLogik E2242, at IP address
192.168.127.154. Also, make sure you are logged in on the Server Settings tab. Go to the Click&Go
Logic tab.
2. Double click #0 in the Rule-set. The Logic Configuration window will appear.
3. Make sure that Enable in the upper left hand corner is checked.
4. Select Enable peer-to-peer I/O.
5. Select Input channels mirror to and click remote IP…
6. Select DI as the type to export the signal from the input module. In the 1. Dest. IP: field, enter
192.168.127.3 and click OK to save this setting.
7. Click OK to close the Logic Configuration window.
8. Click Download on the Rule-set Management Bar.
9. Select Yes when asked to restart and wait until the server has restarted and is back on-line.
10. Log in on the Server Settings tab, then go to the Click&Go Logic tab.
11. Click Run on the Rule-set Management Bar. The RDY LED will be flashing green, showing that the ioLogik
is now operating as an Active Ethernet I/O server, using the rule-set that was just defined.