OFF-Delay
Conversely, OFF-Delay keeps the action on running for a period of time from when the IF function is triggered
to when the THEN action is executed. For example, after pushing a button to switch off the light in a lobby, the
light stays ON for an additional 10 seconds before turning OFF so that the user can have enough time to walk
out of the building.
Using Internal Registers
Soft-key
The Internal Registers can be used to ensure that the output is under control. For example, an output can only
be triggered when the local push button is attached to a digital input and the internal register is set.
In this example, the logic between the two IF conditions is AND.”
Remote Control
If an output channel is coordinated by an IF condition, it is limited to the Click&Go logic and can not be
controlled by a remote PC. Users must use Internal Registers to set local and remote control for a designated
output channel. For example, an emergency alarm siren is triggered remotely by a SCADA system when
detecting high pressure or leaks. If the network is down, a local shutdown button can also be switched ON to
sound the alarm.
In this example, the logic between the two IF conditions is OR”.
NOTE
Inter Register can be controlled by Modbus/TCP protocol, refer to the appendix for the addressed list for all the
Internal Registers.