Click&Go V2 Click&Go Examples and Applications
4-30
NOTE
Receiving this Remote Action
will disable the local (site) Alarm Light
Click&Go Programming Example_Central
I/O Alias and Timer Configuration of ioLogik_Central
1. Digital Input DI_0: Site #001 Ack, Button.
2. Digital Output DO_0: Site #001 Alarm Light.
Programming Manners of ioLogik E2210_Central
1. Switch on the specific Alarm Light when an alarm from that site is activated.
2. Switch on the Alarm Speaker when an alarm from any site is activated.
3. An Acknowledge Button is used to disable the local (central) alarm light, local Alarm Speaker, and the
remote (site) Alarm Light.
Click&Go Rule-set of ioLogik E2210_Central
Logic #0 - Receiving Remote Action from ioLogik E2210_Site