WORKING SETPOINT AND CONFIGURATION PARAMETERS (EVERY CONTROL)
Setting the working setpoint
press LED will flash
press or , within 15 seconds to change the temperature value.
after changing the value, confirm by pressing , or avoiding any operation for 15 seconds.
You also can modify the working setpoint through parameter SP.
Working setpoints
LABEL
MIN.
MAS.
U.M.
DEF.
WORKING SETPOINTS
r1
r2
°C/°F (1)
0
working setpoint
Setting configuration parameters
To gain access the procedure:
make sure no procedure is running
press and 4 s: the display will show “PA
press
press or in 15 s to set “-19
press or do not operate 15 s
press and 4 s: the display will show “SP
To select a parameter:
press or
To modify a parameter:
press
press or in 15 s
press or do not operate 15 s.
To quit the procedure:
press and 4 s or do not operate 60 s.
Configuration parameters
LABEL
MIN.
MAS.
U.M.
DEF.
WORKING SETPOINTS
SP
r1
r2
°C/°F (1)
0
working setpoint
LABEL
MIN.
MAS.
U.M.
DEF.
MEASURE INPUTS
CA1
-25
25
°C/°F (1)
-1
cabinet probe offset
P0
0
1
-
1
kind of probe (0=PTC, 1=NTC)
P1
0
1
-
0
decimal point Celsius degree (for the quantity to show during the normal operation) (1=
YES)
P2
0
1
-
0
unit of measure temperature (2) (0=°C, 1=°F)
LABEL
MIN.
MAS.
U.M.
DEF.
MAIN REGULATOR
r0
0.1
15
°C/°F (1)
3
working setpoint differential
r1
-99
r2
°C/°F (1)
0
minimum working setpoint
r2
r1
99
°C/°F (1)
10
maximum working setpoint
LABEL
MIN.
MAS.
U.M.
DEF.
COMPRESSOR PROTECTIONS
C0
0
240
min
0
compressor delay since you turn on the instrument
C2
0
240
min
3
minimum time the compressor remainsturned off
LABEL
MIN.
MAS.
U.M.
DEF.
DEFROST
d0
0
99
H
6
defrost interval; also look at d8 (5)
0=the defrost at intervals will never be activated
d3
0
99
min
20
defrost duration (0=the defrost will never be activated)
d4
0
1
-
0
defrost when you turn on the instrument (1=YES)
d5
0
99
min
0
defrost delay when you turn on the instrument (only if d4 = 1)
d6
0
1
-
1
temperature shown during the defrost
0=cabinet temperature1=if to the defrost activation the cabinet temperature is below
“working setpoint+ r0”, at most “working setpoint + r0”; if to the defrost activation the
cabinet temperature is above “working setpoint +r0”, at most the cabinet temperature to
the defrost activation (6)
(1) the unit of measure depends on parameter P2
(2) set the parameters related to the regulators appropriately after themodification of the parameter P2
(5) the modification of parameter d0 has effect since the end of the previous defrost interval or since the activation of a defrost by hand
(6) the display restores the normal operation as soon as the defrost ends and the cabinet temperature falls below the one that has locked the display (or if a
temperature alarm arises)