Sagi KUB2A (внутренний агрегат) [34/130] Use the keys to select the new value applicable to parameters only

Sagi KUB2A (внутренний агрегат) [34/130] Use the keys to select the new value applicable to parameters only
16
dE
defrost interval count:
0= actual hours; 1=hours comp. ON; 2= autodeterm.
0
0
0
2
dP
protection defrost interval (0= de-activated)
24 ore
24 ore
0
72
A0
alarm hysteresis (differential)
+2 °C
+2 °C
1
15
A1
min. operating setpoint alarm (0= excluded)
-2 °C
-2 °C
-55
0
A2
max. operating setpoint alarm (0= excluded)
+15 °C
+15 °C
0
+99
A3
alarm exclusion from device start
120 min
120 min
0
240
A4
buzzer activation mode for alarm : 0= always; 1= timer-controlled
1
1
0
1
A5
time limit for buzzer acoustic signal (only if A4 = 1)
1 min
1 min
0
240
A6
temperature alarm exclusion time (only if A1 and/or A2 0)
15 min
15 min
0
240
A7
temp. alarm exclusion time after evap. stop (for A1 and/or A2 0)
60 min
60 min
0
240
F1
temper. above which the evap. fan stops
(only if /A = 1 and F7 = 3 or 4)
-1°C
-1°C
-55
+99
F2
fan differential (relating to F1, only if /A = 1 and F7 = 3 or 4)
+2°C
+2°C
1
15
F3
evaporator fan func. during regular operation (0=OFF; 1=ON; 2=parallel with
compressor; 3=determined by F1 and F2 with comp. ON and OFF with comp. OFF
1
1
0
4
F4
evap. vent. operation during defrost and dripping (0= OFF, 1= ON, 2= determ. with F7)
0
0
0
2
F5
evaporator fan stop after dripping
3 min
3 min
0
15
F6
temperature below which the condenser fan turns off
20 °C
20 °C
-55
+99
F7
evap. vent. operation during standard oper. (0= OFF, 1= ON, 2= parallel with comp.,
3= determined with F1 and F2, 4= determined with F1 and F2 with comp. ON, OFF
with comp. OFF)
+3°C
+3°C
0
4
F8
condenser fan func. during regular operation (0=parallel with compr.; 1=ON); also refer
to F6 and F7
0
0
0
1
F9
condenser fan func. during defrost and dripping (0=OFF; 1=ON, 2=ON if Tc≥35°C and
OFF if Tc<33°C)
0
0
0
2
FA
critical temperature for signalling high condensation temperature
55°C
55°C
-55
+99
Fb
critical temperature for high pressure akarm
57°C
57°C
-55
+99
P0
Configuration parameters printing enable (0 = disabled)
1
1
0
1
P1
Sampling time (see also parameter P6)
30 min/ore
30 min/ore
1
60
P2
Selection of temperature probe to be printed (0 = none, 1=chamber probe, 2 =
chamber and evaporator probe, 3 = all)
1
1
0
3
P3
Payslip heading selection (0 =excluded, 1= Refrigerator, 2=Refrigerated counter)
2
2
0
2
P4
Equipment identification number printing enable (0 = no, 1= yes)
1
1
0
1
P5
Selection of language for payslip heading (1 = Italian, 2 = English, 3 = French, 4 =
Spanish, 5 = German)
1
1
-1
5
P6
Selection of unit of measure for sampling time (1 = minutes, 2 =hours)
1
1
1
2
L1
Instrument address (date detected in printing phase if P4 = 1)
1
1
0
256
L2
Serial port management (o = not utilised, 1 = print)
1
1
0
1
L3
Baud Rate data transmiss. (1=2400, 2=4800, 3=9600, 4=18200)
3
3
1
4
L4
Transmission control mode (0 = no parity, 1 = odd, 2 = even)
0
0
0
2
USER PARAMETER CONFIGURATION - PROBE READING
Press the on/sby/enter key over 5 secods (thus avoiding Sby) to gain access to probe reading
and user parameter list.
The display shows the first label “Pd
Use the up and down keys to scroll probe and parameter reading.
Press the on/sby/enter key to confirm your selection and enter the mode for reading probes or
changing parameters.
The current value blinks on the display.
Use the keys to select the new value, applicable to parameters only.
Press the on/sby/enter key to exit or confirm the selection of the parameter new value; the
setting stops blinking.
You can leave the programming phase by waiting for 30 seconds without operating on the card, or pressing for 5 seconds.
In both cases, there you will hear 3 consecutive, short beeps and the display will temporarily show [ESC].