WORKING SETPOINT AND CONFIGURATION PARAMETERS (ELIWELL)
Setting the working setpoint
Access the “Machine Status” menu by pressing and quickly releasing the key.
The label of the SEtfolder appears.
To display the Setpoint value press the key again. The value appears on the display.
To change the Setpoint value, use the and keys within 15 seconds.
after changing the value, confirm by pressing .
How to set the configuration parameters
Configuration parameters are arranged on two levels.
If you have to gain access the first level:
press for than 5 sec
If you have to select a parameter:
press or
If you have to modify the value of the parameter:
press
press or in 15 s
press or do not operate 15 s
If you have to gain access the second level:
gain access the first level
press or for selecting “PA2
press and or for setting 15.
press or do not operate 15 s
If you have to quit the procedure:
press or do not operate 15 s
PAR.
DESCRIPTION
RANGE
DEFAULT
LEVEL*
U.M.
Set
Temperature SEtpoint.
-50…99
0
°C/°F
COMPRESSOR
diF
diFferential. Relay compressor tripping differential. The compressor stops on reaching
the Setpoint value (as indicated by the adjustment probe), and restarts at temperature
value equal to the Setpoint plus the value of the differential. Note: the value 0 cannot be
assumed
0.1...30.0
3
1&2
°C/°F
HSE
Higher SEt. Maximum possible setpoint value
-50…230
10
1&2
°C/°F
LSE
Lower SEt. Minimum possible setpoint value
-55…99
0
1&2
°C/°F
OSP
Offset Set Point. Temperature Value to be added to the Set-Point if reduced set is
enabled (Economy function).
-30…30
0
2
°C/°F
HC
digital (input) Open door. Digital input that allow you to switch off loads. Valid if H11 = ±4
(door switch). n = does not switch off loads; y = switch off loads.
h/c
c
2
flag
dOd
digital (input) Open door. Ingresso digitale che permette di spegnere le utenze.
Valido se H11 = ±4 (micro porta). n = non spegne le utenze; y = spegne le utenze.
n/y
n
2
flag
dAd
digital (input) Activation delay. Delay time in activating the digital input.
0…255
0
2
min
Ont
ON time (compressor). Compressor activation time in the event of faulty probe. If OFt=1
and Ont=0, the compressor is always off, while if OFt=1 and Ont>0 it operated in duty
cycle mode.
0...250
6
2
min
OFt
OFF time (compressor). Compressor deactivation time if probe is faulty. If Ont=1 and
OFt=0, the compressor is always on, while if Ont=1 and OFt>0 it operated in duty cycle
mode.
0...250
6
2
min
dOn
delay (at) On compressor. Delay time in activating the compressor relay after switch-on
of instrument.
0...250
0
2
secs
dOF
delay (after power) OFF. Delay after switch off; the indicated time must elapse between
switch-off of the compressor relay and the successive switch-on.
0...250
3
2
min
dbi
delay between power-on. Delay between switch-ons; the indicated time must elapse
between two successive switch-ons of the compressor.
0...250
5
2
min
OdO
delay Output (from power) On. Delay time in activating the outputs after switch-on of the
instrument or after a power failure.
0...250
0
2
min
DEFROST
dit
defrost interval time. Interval between the start of two successive defrosting operations.
0...250
6
1&2
hours
dCt
defrost Counting type. Selection of count mode for the defrosting interval.
0 = compressor operating hours (DIGIFROST® method);
Defrosting active only if compressor is on;
0/1/2
1
2
num