Mitsubishi Electric PURY-RP200YJM-A [11/31] Lifting method
![Mitsubishi Electric PURY-RP200YJM-A [11/31] Lifting method](/views2/1331598/page11/bgb.png)
11
GB
6. Space required around unit
1 In case of single installation
Secure enough space around the unit as shown in the fi gure on page 2.
[Fig. 6.0.1] (P.2)
<A> Top view <B> Side view
<C> When there is little space up to an obstruction
A
Front
B
Unit height
C
Back
D
Air outlet guide (Procured at the site)
(1) If the distance is 300 mm or more between the rear side and the wall
(2) If the distance is 100 mm or more between the rear side and the wall
(3) If the wall height (H) of the front, rear or side exceeds the wall height
restriction
When the height of the walls on the front, back or on the sides <H> exceeds
the wall height limit as defi ned here, add the height that exceeds the height
limit <h> to the fi gures that are marked with an asterisk.
•
•
<Wall height limit> Front: Up to the unit height
Back: Up to 500 mm from the unit bottom
Side: Up to the unit height
(4) If there are obstacles at the upper part of the unit
2 In case of collective installation
[Fig. 6.0.2] (P.2)
A
Front
B
Must be open
C
Wall height (H)
When multiple units are installed adjacent to each other, secure enough
space to allow for air circulation and walkway between groups of units as
shown in the fi gures on page 2.
At least two sides must be left open.
As with the single installation, add the height that exceeds the height limit
<h> to the fi gures that are marked with an asterisk.
If there is a wall at both the front and the rear of the unit, install up to 6 units
consecutively in the side direction and provide a space of 1000 mm or more
as inlet space/passage space for each 6 units.
•
•
•
•
[Fig. 7.0.1] (P.2)
Use suspension ropes that will withstand the weight of the unit.
When moving the unit, use a 4-point suspension, and avoid giving impacts
to the unit (Do not use 2-point suspension).
Place protective pads on the unit where it comes in contact with the ropes to
protect the unit from being scratched.
Set the angle of roping at 40° or less.
Use 2 ropes that are each longer than 8 meters.
•
•
•
•
•
Place protective padding at the corners of the product to protect the product
from scratches or dents that might be caused by the rope.
Caution:
Be very careful when carrying/moving the product.
- When installing the outdoor unit, suspend the unit at the specifi ed location of
the unit base. Stabilize as necessary so that it does not move to the side and
support it at 4 points. If the unit is installed or suspended with 3-point support,
the unit may become unstable and fall.
•
7. Lifting method
3. Combination of outdoor units
The unit described in this manual cannot be used in combination. It is designed to be used as a single unit.
Outdoor unit model Component unit model
PURY-RP200YJM-A(-BS) - -
PURY-RP250YJM-A(-BS) - -
PURY-RP300YJM-A(-BS) - -
4. Specifi cations
Model
PURY-RP200YJM-A PURY-RP250YJM-A PURY-RP300YJM-A
Noise level (50/60Hz)
56dB <A> 57dB <A> 59dB <A>
External static pressure
0 Pa *2
Indoor units
Total capacity
50~150% *1
Model
15~250
Quantity
1~20 1~25 1~30
Operation
temperature
Standard type
Cooling mode: – 5°CDB ~ 43°CDB
Heating mode: – 20°CWB ~ 15.5°CWB
Fresh air intake type
Cooling mode: 21°CDB ~ 43°CDB
Heating mode: – 12.5°CWB ~ 20°CWB
*1: The total indoor capacity of units run simultaneously is 150% or less.
*2: To enable high static pressure with RP200, RP250, RP300, set the DipSW on the main panel as follows.
SW3-9: ON, SW3-10 60Pa compatible: OFF, 30Pa compatible: ON
5. Confi rmation of parts attached
This unit includes the following parts. Please check.
For usage methods, refer to item 10.2.
1 Connecting pipe
ID ø25.4, ID ø28.58
<Low-pressure side>
Model RP200 1 pc.
RP250 1 pc.
RP300 1 pc.
•
•
Содержание
- Air conditioners for building application outdoor unit 1
- For use with r410a 1
- Pury rp yjm a bs 1
- A shape 5
- Fig 10 5
- Id ø25 5
- Id ø28 8 ø28 8 5
- Low pressure side 5
- Rp200 rp250 rp300 5
- A b d c 6
- Fig 10 6
- Fig 10 fig 10 6
- A cable strap 7
- A power source 7
- Address 7
- B power source cable 7
- B transmission line 7
- C earth screw 7
- C transmission cable 7
- Change the jumper connec tor from cn41 to cn40 1 7
- Control box 7
- Keep the jumper connector on cn41 7
- Power supply terminal block tb1 7
- Sw2 1 on 2 7
- System controller 7
- A b a b 8
- B a 220 240v l n 8
- B a c 3n 380 415v 8
- Fig 11 8
- M1m2 s 8
- M1m2 s m1 m2 tb3 8
- M1m2 s tb7 8
- System controller 8
- Before installation and electric work 9
- Caution 9
- Contents 9
- High voltage warning 9
- Safety precautions 9
- Symbols used in the illustrations 9
- Symbols used in the text 9
- Warning 9
- About the product 10
- Before installation 10
- Before installation relocation electrical work 10
- Before starting the test run 10
- Caution 10
- Precautions for devices that use r410a refrigerant 10
- Caution 11
- Combination of outdoor units 11
- Confi rmation of parts attached 11
- Lifting method 11
- Space required around unit 11
- Specifi cations 11
- Caution 12
- Installation 12
- Installation of unit 12
- Refrigerant piping installation 12
- Warning 12
- Additional refrigerant charge 13
- Calculation of additional refrigerant charge 13
- Refrigerant piping system 13
- Caution 14
- Precautions concerning piping connection and valve operation 14
- Warning 14
- Airtight test evacuation and refrigerant charging 15
- Caution 15
- Caution 16
- Control box and connecting position of wiring 16
- Penetrations 16
- Thermal insulation of refrigerant piping 16
- Wiring for details refer to the installation manual of each unit and controller 16
- Example of a group operation system with multiple outdoor units shielding wires and address setting are necessary 17
- Wiring transmission cables 17
- Warning 18
- Wiring of main power supply and equipment capacity 18
- Caution 19
- Information on rating plate 19
- Test run 19
- The following phenomena do not represent faults 19
- Внимание 20
- До установки и монтажа проводки 20
- Меры предосторожности 20
- Предупреждение 20
- Предупреждение о высоком напряжении 20
- Символы используемые в иллюстрациях 20
- Символы используемые в тексте 20
- Содержание 20
- Информация об изделии 21
- Меры предосторожности для приборов в которых используется хладагент r410a 21
- Перед монтажом или переносом проводки 21
- Перед началом тестового запуска 21
- Перед установкой 21
- Внимание 22
- Комбинация наружных блоков 22
- Подтверждение комплектности 22
- Способ поднимания 22
- Технические характеристики 22
- Требования к пространству вокруг блока 22
- Внимание 23
- Предупреждение 23
- Установка 23
- Установка блока 23
- Установка трубопроводов 23
- Зарядка дополнительного количества хладагента 24
- Расчет необходимого количества хладагента 24
- Установка трубопроводов хладагента 24
- Внимание 25
- Меры предосторожности при соединении труб и работе с клапанами 25
- Предупреждение 25
- Внимание 26
- Проверка на герметичность вакуумирование и зарядка хладагентом 26
- Блок управления и места подсоединения проводки 27
- Внимание 27
- Отверстия 27
- Проводка для получения информации см руководство по установке каждого блока и пульта управления 27
- Термоизоляция труб хладагента 27
- Подсоединение кабелей передачи данных 28
- Пример комплексной системы с несколькими наружными блоками необходимо экранирование проводки и назначение адресов 28
- Подсоединение основной проводки питания и характеристики оборудования 29
- Предупреждение 29
- Внимание 30
- Информация на табличке параметров 30
- Следующие явления не являются признаками неисправности 30
- Тестовый запуск 30
Похожие устройства
- Mitsubishi Electric PURY-RP200YJM-A Сертификат
- ТОРГМАШ М-50С Инструкция по эксплуатации
- ТОРГМАШ М-50С Сертификат
- ТОРГМАШ М-50С Каталог оборудования ТОРГМАШ
- Mitsubishi Electric PLFY-P15VCM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P15VCM-E Инструкция по установке
- Mitsubishi Electric PLFY-P15VCM-E Сертификат
- Mitsubishi Electric PKFY-P50VHM-E Инструкция по эксплуатации
- Mitsubishi Electric PKFY-P50VHM-E Инструкция по установке
- Mitsubishi Electric PKFY-P50VHM-E Сертификат
- Mitsubishi Electric PLFY-P32VCM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P32VCM-E Инструкция по установке
- Mitsubishi Electric PLFY-P32VCM-E Сертификат
- Mitsubishi Electric PKFY-P32VHM-E Инструкция по эксплуатации
- Mitsubishi Electric PKFY-P32VHM-E Инструкция по установке
- Mitsubishi Electric PKFY-P32VHM-E Сертификат
- Mitsubishi Electric PKFY-P40VHM-E Инструкция по эксплуатации
- Mitsubishi Electric PKFY-P40VHM-E Инструкция по установке
- Mitsubishi Electric PKFY-P40VHM-E Сертификат
- Mitsubishi Electric PLFY-P100VBM-E Инструкция по эксплуатации