Omron VZAB0P4BAA [11/218] Wiring specification

Omron VZA43P0BAA [11/218] Wiring specification
3 Electrical Installation
10 I67E-EN V1000 Quick Start Guide
Wiring Specification
Main Circuit
Use the fuses and line filters listed up in the table below when wiring the main cir-
cuit. Make sure not to exceed the given tightening torque values.
Tightening Torque Values
Tighten the main circuit terminals using the torque values provided by the table be-
low.
Model
VZA*
<1> For UL compliance a different fuse type has to be used. For details refer to the instruction manual.
EMC Filter Type
Main Fuse
(Ferraz)
Recom.
Motor
cable
[mm²]
Main Circuit Terminal Sizes
Rasmi Schaffner
R/L1,S/L2,T/L3,
U/T1,V/T2,W/T3,
- , +1, +2
B1, B2 GND
B0P1
A1000-FIV1010-RE A1000-FIV1010-SE
TRS5R 1.5 M3.5 M3.5 M3.5
B0P2 TRS10R 1.5 M3.5 M3.5 M3.5
B0P4 TRS20R 1.5 M3.5 M3.5 M3.5
B0P7
A1000-FIV1020-RE A1000-FIV1020-SE
TRS35R 2.5 M4 M4 M4
B1P5 TRS50R 4 M4 M4 M4
B2P2 A1000-FIV1030-RE A1000-FIV1030-SE TRS60R 4 M4 M4 M4
B4P0 under development
20P1
A1000-FIV20010-
RE
A1000-FIV20010-SE
TRS5R 1.5 M3.5 M3.5 M3.5
20P2 TRS5R 1.5 M3.5 M3.5 M3.5
20P4 TRS10R 1.5 M3.5 M3.5 M3.5
20P7 TRS15R 1.5 M3.5 M3.5 M3.5
21P5
A1000-FIV2020-RE A1000-FIV2020-SE
TRS25R 2.5 M4 M4 M4
22P2 TRS35R 4 M4 M4 M4
24P0 A1000-FIV2030-RE A1000-FIV2030-SE TRS60R 4 M4 M4 M4
25P5
A1000-FIV2060-RE A1000-FIV2050-SE
A6T70
<1>
6M4M4M5
27P5
A6T100
<1>
10 M4 M4 M5
2011
A1000-FIV2100-RE -
A6T150
<1>
16 M6 M5 M6
2015
A6T200
<1>
25 M8 M5 M6
40P2
A1000-FIV30005-
RE
A1000-FIV30005-SE
TRS2.5R 2.5 M4 M4 M4
40P4 TRS5R 2.5 M4 M4 M4
40P7
A1000-FIV3010-RE A1000-FIV3010-SE
TRS10R 2.5 M4 M4 M4
41P5 TRS20R 2.5 M4 M4 M4
42P2 TRS20R 2.5 M4 M4 M4
43P0 TRS20R 2.5 M4 M4 M4
44P0 A1000-FIV3020-RE A1000-FIV3020-SE TRS30R 4 M4 M4 M4
45P5
A1000-FIV3030-RE A1000-FIV3030-SE
A6T50
<1>
4M4M4M5
47P5
A6T60
<1>
6M4M4M5
4011
A1000-FIV3050-RE -
A6T70
<1>
10 M5 M5 M5
4015
A6T80
<1>
10 M5 M5 M6
Terminal Size M3.5 M4 M5 M6 M8
Tightening Torque [Nm] 0.8 to 1.0 1.2 to 1.5 2.0 to 2.5 4.0 to 5.0 9.0 to 11.0