Tecorp HC2V9G4220 [66/182] Group p1 main and auxiliary reference parameter

Tecorp HC2V8G4315 [66/182] Group p1 main and auxiliary reference parameter
High Performance Vector Control/Torque Control Inverter User Manual
44 Chapter 5 List of Parameters
Function
code
number
Function code name
Factor
y
setting
Setting range
Unit
Property
Function code selection
User
setting
process close loop control;
3: Composite control;
Vector control 2 without
encoder speed feedback:
4: Process open loop control
5: Analog value feedback
process close loop control;
6: Single phase pulse feedback
process close loop control;
7: Composite control;
Vector control 2 with encoder
speed feedback:
8: Process open loop control
P0.04
Open loop main reference
mode
0 0 ~ 4 / ×
0: Open loop digital frequency
reference (P0.05);
1: AI1 analog value reference;
2: AI2 analog value reference;
3: AI3 analog value reference;
4: DI pulse reference
P0.05
Open loop digital frequency
reference
50.00
0.00 ~ 300.00
Hz
Upper / lower frequency limit
(P0.13 ~ P0.14)
P0.06
Running command
reference mode
0 0 ~ 2 /
0: Operation panel;
1: Terminal;
2: Host computer
P0.07
Running direction
command
0 0 ~ 1 / 0: Run forward; 1: Run reverse
P0.08
Acceleration time 0 6.0 15kW and below
P0.09
Deceleration time 0 20.0
0.1 ~ 3600.0 s
18.5kW and above
0.1 ~
3600.0s
P0.10
S-curve time 0.0 0.0 ~ 3600.0 s 0.0 ~ 3600.0s
P0.11 Maximum output frequency
50.00
0.01 ~ 300.00
Hz ×
Upper frequency limit P0.13 ~
300.00Hz
P0.12 Maximum output voltage 380 1 ~ 480 V × 1 ~ 480V
P0.13 Frequency upper limit 50.00
0.00 ~ 300.00
Hz ×
Lower frequency limit P0.14 ~
Maximum output frequency
P0.11
P0.14 Frequency lower limit 0.00 0.00 ~ 300.00
Hz ×
0.00Hz ~ Upper frequency limit
P0.13
P0.15 Basic operating frequency
50.00
0.00 ~ 300.00
Hz ×
0.00Hz ~ Maximum output
frequency P0.11
P0.16 Torque boost 0.0 0.0 ~ 30.0 % ×
0.0: Auto torque boost;
0.1% ~ 30.0%
Group P1 Main and Auxiliary Reference Parameter
P1.00
Open loop auxiliary
reference mode
0 0 ~ 4 / ×
0: None
1: AI1; 2: AI2; 3: AI3; 4: DI
P1.01
Open loop reference main
and auxiliary relation
calculation
0 0 ~ 5 / ×
0: Main + Auxiliary;
1: Main - Auxiliary;
2: Auxiliary-50%;
3: Main + Auxiliary-50%;
4: Take maximum value;
5: Take minimum value
P1.02
A
nalog feedback close loop
control main reference
mode
0 0 ~ 4 / ×
0: Digital voltage reference
P8.00;
1: AI1; 2: AI2;
3: AI3; 4: DI
P1.03
A
nalog feedback close loop
control auxiliary reference
mode
0 0 ~ 4 / ×
0: None;
1: AI1; 2: AI2;
3: AI3; 4: DI
P1.04
A
nalog feedback close loop
control reference main and
0 0 ~ 5 / ×
0: Main + Auxiliary;
1: Main - Auxiliary;

Содержание